Specifications; Input; Output; General - Victron energy SKYLLA 24/100 3-PHASE CE User Manual

Table of Contents

Advertisement

9. SPECIFICATIONS

9.1 Input

Input voltage
Input voltage range
Frequency range
Input fuse
Cos-phi
Input power

9.2 Output

Nominal charging voltage
High charging voltage (boost)
Low charging voltage (float)
Output voltage range
Charging characteristic
Voltage stability
Output current
Output current limit level range
Output current stability
Short circuit protection
Voltage sensing capability

9.3 General

EMC
Emission
Immunity
Operating temperature range
Cooling
Noise level
Case
Colour
Dimensions (h x b x d)
Weight
Humidity
Altitude
victron energy
3 x 380Vac 3-phase
(3 x 415 Vac 3-phase optional)
(3 x 440 Vac 3-phase optional)
+/- 10% (+10% to -25% to remain functional)
47 - 65Hz
16A automatic switch
0,93 at nominal load
3.63 kWatt with nominal output load (28.5Vdc, 100A)
24 Vdc
28,5 Vdc
26,5 Vdc
24 - 30 Vdc
IUOUO in accordance with DIN 41772
1%
100A
60-100% of nominal output current (standard adjustment 100%)
+/- 5 %
Continuous short circuit proof
Compensates voltage drop in the battery cable
Electro-magnetic comparability according to the Council Directive 89/336 EEC
EN50081-2 (1993)
EN50082-2 (1994)
o
-10 to 40
C, 100% of nominal output current
o
-10 to 50
C, 80% of nominal output current
o
-10 to 55
C, 60% of nominal output current
The output current is limited automatically in case of overheating
Forced air cooling, temperature regulated
<< 40 dB(A)
Aluminium IP20
Blue (RAL5012) epoxy
490 x 350 x 280
42 kg
95%
1000m before derating is required
manual Skylla 24/100 3F
Page 15

Advertisement

Table of Contents
loading

Table of Contents