Our proven philosophy has resulted in a full range of state-of-the-art equipment for the supply of electrical power. All our equipment meets the most stringent requirements. Victron Energy systems provide you with high-quality AC supplies at places where there are no permanent sources of mains power.
The maximum charging current is 100A and the recommended battery capacity is 500 - 1000Ah. The charger is suitable for traction batteries. Please consult your local Victron Energy agent for more details.The Skylla 24/100 3-phase charger is a fully automatic battery charger. It is powered by 380Vac 50/60 Hz nominal mains supply.
The Skylla 24/100 3-phase has a temperature compensation facility which adjusts the charger voltage to the battery temperature. In order to use this facility, a Victron Energy temperature sensor must be fitted to the battery. This is because a higher charging voltage can be used with a cold battery than with a warm battery. The reference charging voltage is 28.5Vdc at a battery temperature of 20...
Cable lengths in excess of 6 meters are not recommended. Length cross section 0 - 1.5 meters 35 mm 1.5 - 6 meters 50 mm victron energy manual Skylla 24/100 3F Page 7...
The “High rate” LED on the front panel will illuminate after the battery voltage has reached its nominal voltage level. (Boost level) If a temperature sensor is used, refer to chapter 4.1. If voltage sensing is used, refer to chapter 4.1. The charger is ready to be used now. victron energy Page 8 user manual Skylla 24/100 3F...
For the use of battery room ventilators, there are two potential-free changeover contacts. When the charger is in boost, the contacts E11, E12 & E14, E15 will be closed. See drawing SK07010E. victron energy manual Skylla 24/100 3F Page 9...
If the LED is not on, the charger is in current limit mode. Wait until the LED is on again and readjust the float output level potentiometer. The float level is now adjusted. Illustration 11. Adjusting the float (R12) voltage level. victron energy Page 10 user manual Skylla 24/100 3F...
These values may concern matters such as voltage, frequency or switch on sensitivity. The screw must be turned by means of a screwdriver (No. 0). See also illustration 12. Illustration 12. Jumper and potentiometer. victron energy manual Skylla 24/100 3F Page 11...
The following conditions are covered by the diagrams: battery charger does not function at all batteries are not being fully charged batteries are being overcharged victron energy Page 12 user manual Skylla 24/100 3F...
Noise level << 40 dB(A) Case Aluminium IP20 Colour Blue (RAL5012) epoxy Dimensions (h x b x d) 490 x 350 x 280 Weight 42 kg Humidity Altitude 1000m before derating is required victron energy manual Skylla 24/100 3F Page 15...