These wiring connections must be made with particular care and meet or
exceed the nominal current and power specifications; the current flowing
through them is 2.5 A per JOYA Cradle Dispenser. The wires must meet the
Safety Normatives currently in force.
The following table indicates the maximum current specifications for some wire
conductor sections according to the EN 60950 Electrical Safety Normative.
Maximum Current
10 A
16 A
25 A
Suggestion:
It is advised to use a cable made up of two groups of three-conductor multi-
stranded wire with flame retardant insulation (single or together in a cable with
flame retardant insulation) having a copper wire section equal to 1.5 mm².
The two groups of three conductors are connected to the output terminals of
the power supplies: in the case of two power supplies, one group of wires is
connected to one power supply and the other group is connected to the other
power supply; in the case of a single power supply, both groups of wires are
connected to the same power supply.
Each three conductor cable group must be used to connect four of the JOYA
Cradle Dispensers mounted in the Base Unit via their junction cables.
JOYA Cradle Dispenser junction cables can be connected to the three-
conductor cable groups using IDC connectors having a maximum current
capability not less than 3 A.
5
Wire Section
1 mm²
1.5 mm²
2.5 mm²