Daikin VRV III REMQ72PBYD Engineering Data page 50

Table of Contents

Advertisement

EDUS391004-N
Name
Clamp(1)
Clamp(2)
Clamp(3)
Vinyl tube
9 pcs.
3 pcs.
1 pc.
Quantity
Shape
(Small)
(Large)
Liquid side
Liquid side
Name
accessory pipe (1)
accessory pipe (2)
1 pc.
1 pc.
Quantity
Shape
72~120P
144P 72~120P
144P 72~120P
(Refer to figure 1)
1. Clamps, Manuals, etc.
2. Accessory pipes
2-3 Option accessory
To install the outdoor units, the following optional parts are also
required. To select an optimum kit, refer to "6. REFRIGERANT
PIPING".
• Outdoor unit multi connection piping kit
Number of outdoor units connected
Kit name
• Refrigerant branching kit
REFNET header KHRP26M22H9 KHRP26M33H9 KHRP26M72H9 KHRP26M73HU9
REFNET joint
KHRP26M22T KHRP26M33T KHRP26M72TU9 KHRP26M73TU9
Make sure that any separately purchased accessories are designed
for use with R410A.
2-4 Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of
specifications.
2-5 Main components
For main components and function of the main components, refer to
the Engineering Data Book.
3.
SELECTION OF LOCATION
Select a location for installation that meets the following conditions
and get the customer's permission.
1.
Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturb anyone.
2.
The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
3.
The piping length between the outdoor unit and the indoor unit may
not exceed the allowable piping length.
(Refer to "6. REFRIGERANT PIPING")
4.
Locations where the unit's suction vent and outlet vent do not
generally face the wind.
Wind blowing directly into the suction or outlet vents will interfere
with the unit's operation.
If necessary, install some kind of obstruction to block the wind.
5.
The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available.
(See the "Installation Space Examples" for the minimum space
requirements.)
Installation Space Examples
• The installation space requirement shown in figure 2 is a reference
for cooling operation when the outdoor temperature is 95°F.
If the design outdoor temperature exceeds 95°F or the heat load
exceeds maximum capacity in all the outdoor unit, take an even
large space on the intake shown in figure 2.
• During installation, install the units using the most appropriate of
the patterns shown in figure 2 for the location in question, taking
into consideration human traffic and wind.
Installation of Outdoor Units
Conduit mounting plate
Manuals, etc.
4 pcs.
2 pcs.
2 pcs.
1 pc. each
• Operation manual
• Installation manual
• "REQUEST FOR THE
INDICATION" label
(Installation records)
Gas side
Gas side
L type accessory
accessory pipe (1)
accessory pipe (2)
joint
1 pc.
1 pc.
144P
144P only
2 units
3 units
BHFP22P100U BHFP22P151U
• If the number of units installed is more than that shown in the
pattern in figure 2, install the units so there are no short circuits.
• As regards space in front of the unit, consider the space needed
for the local refrigerant piping when installing the units.
• If the work conditions in figure 2 do not apply, contact your dealer
or Daikin directly.
(Refer to figure 2)
1. Front side
2. No limit to wall height
3. Service space of front side
4. Service space of suction side
1 pc.
For Patterns 1 and 2 in figure 2 :
Wall height for front side – no higher than 59 in.
Wall height on the suction side – no higher than 19-5/8 in.
Wall height for sides – no limit.
If the height is exceeded the above, calculate h1 and h2 shown
in the figure below, and add h2/2 to the service space of front
side and h1/2 to the service space of suction side.
DANGER
• Do not install unit in an area where flammable materials are
present due to risk of explosion resulting in serious injury
or death.
• Refrigerant gas in heavier air and replaces oxygen. A massive
leak could lead to oxygen depletion, especially in basements,
and an asphyxiation hazard could occur leading to serious
injury or death.
Refer to the chapter "CAUTION FOR REFRIGERANT LEAKS".
NOTE
1.
An inverter air conditioner may cause electronic noise generated
from AM broadcasting. Examine where to install the main air
conditioner and electric wires, keeping proper distances away from
stereo equipment, personal computers, etc.
Particularly for locations with weak reception, ensure there is a
distance of at least 10 ft for indoor remote controllers, place power
wiring and transmission wiring in conduits, and ground the
conduits.
(Refer to figure 3)
1. Indoor unit
2. Branch switch, overcurrent breaker
3. Remote controller
4. COOL/HEAT selector
5. Personal computer or radio
2.
When installing in locations where there is heavy snowfall,
implement the following snow measures.
Ensure the base is high enough that intakes are not clogged by
snow.
Remove the rear intake grille to prevent snow from
accumulating on the fins.
4.
INSPECTING AND HANDLING THE
UNIT
• At delivery, the package should be checked and any damage
should be reported immediately to the carrier claims agent.
• When handling the unit, take into account the following :
1.
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
2.
Decide on the transportation route.
3.
If a forklift is to be used, pass the forklift arms through the large
openings on the bottom of the unit. (Refer to figure 4)
<Front side>
<Suction side>
Service
h2
+
19 - 5/8 +
space
2
or more
or more
Installation
h1
2
3P215731-10R
49

Advertisement

Table of Contents
loading

Table of Contents