Installation - Toshiba RAV-SM182CTP-UL Installation Manual

Hide thumbs Also See for RAV-SM182CTP-UL:
Table of Contents

Advertisement

 Installation space
Reserve sufficient space required for installation or service work.
9.8" (250)
or more
 Ceiling height
Model RAV-
Possible installed ceiling height
SM182, SM242, SM302
Up to 13'1" (4.0 m)
SM362, SM422, SM482
Up to 14'1" (4.3 m)
If height of ceiling exceeds 11'5" (3.5 m), hot air becomes difficult to reach the floor surface, and then the change of
setup of high ceiling is necessary.
For the change method of high ceiling, refer to the application control, "Installing indoor unit on high ceiling" in this
Manual.
 Maximum installation height
SM182,
Model RAV-
SM242, SM302
Standard (Factory default)
Up to 11'5" (3.5 m)
High ceiling (1)
Up to 13'1" (4.0 m)
The lighting time of the filter sign (notification of filter cleaning) on the remote controller can be changed according
to installation conditions.
When it is difficult to obtain satisfactory heating due to location place of the indoor unit or the structure of the room,
the detection temperature of heating can be raised.
For change the setup time, refer to the application control, "Filter sign setting" and "To secure better effect of
heating" in this Manual.
 In case of wireless type
Decide the position which remote controller is operated and the installation place.
And then refer to the Installation Manual of the wireless remote controller kit sold separately.
(The signal of the wireless type remote controller can be received within approx. 26'3" (8 m).
This distance is a criterion and varies a little according to capacity of the battery)
• To prevent malfunction, select a place where is not affected by a fluorescent lamp or direct sunlight.
• Two wireless-type indoor units can be set in a room.
15-EN
(Unit: in (mm))
9.8" (250)
or more
SM362,
SET DATA
SM422, SM482
Up to 11'5' (3.5 m)
0000
Up to 14'1" (4.3 m)
0003
4

Installation

CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carring the indoor unit as it is packaged if possible. If carrying the indoor unit unpacked is necessary, use buffering
cloth or other material to not damage the unit.
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
 External dimensions
Upper pipe draw-out port (knockout hole)
Power supply wire take-in port
3.4"
(knockout hole Ø1.6" (Ø40))
(87)
Left drain pipe connecting port
Refrigerant pipe (Liquid side)
Refrigerant pipe (Gas side)
B (Hanging position)
A
Signal receiving unit mounting section
� 8 �
(Unit: in (mm))
8.6"
(218)
2.6"
9.3" (235)
4.3" (109)
(66)
4.1" (102)
5.2" (132)
Drain pipe connecting port
7.6" (192)
Outer dia. : Ø1.1" (27)
3.9"
(98)
C
6.2"
(158)
Remote controller wire take-in port
F
Remote controller wire take-in
D
port (Knockout hole)
E
Power supply wire take-in port
(knockout hole Ø1.6" (Ø40))
Air taking-in port
Left drain pipe draw-out port
(Duct sold separately)
(knockout hole)
(Knockout hole Ø3.6" (Ø92))
Model RAV-
A
B
C
D
37.4"
35.7"
SM182
(950)
(906)
12.9"
10.7"
(328)
(270)
50.0"
48.2"
SM242, SM302
(1270)
(1223)
SM362,
62.5"
60.7"
13.7"
12.0"
SM422,SM482
(1586)
(1540)
(348)
(303)
3.5" (87)
E
F
13.9"
12.4"
(353)
(313)
14.9"
13.2"
EN
(378)
(333)
16-EN

Advertisement

Table of Contents
loading

Table of Contents