Wired
Wireless remote controller
remote
Sensor block display of
controller
receiving unit
display
Main defective parts
Operation Timer
Indication
Ready
Flashing
GR GR OR
P01
ALT
Indoor unit fan error
Outdoor unit discharge
P03
ALT
temp. error
Outdoor unit
P04
ALT
high-pressure system
error
P05
ALT
Open phase detected
P07
ALT
Heat sink overheat
Indoor unit water
P10
ALT
overflow detected
The fan error of the
P12
ALT
indoor unit
P15
ALT
Gas leakage detected
P19
ALT
4-way valve error
High-pressure
P20
ALT
protective operation
P22
ALT
Outdoor unit fan error
Outdoor unit inverter
P26
ALT
Idc activated
Outdoor unit position
P29
ALT
error
P31
ALT
Other indoor unit error
: Lighting
: Flashing
: OFF
: The air conditioner automatically enters the auto-address setting mode.
ALT : When two LEDs are flashing, they flash alternately. SIM : When two LEDs are flashing, they flash in synchronization.
Receiving unit display OR : Orange GR : Green
49-EN
Judging
Parts to be checked / error description
conditioner
device
Indoor fan motor, indoor P.C. board --- Indoor AC
Indoor
fan error (fan motor thermal relay activated) was
Entire stop
detected.
An error was detected in the discharge temp.
Outdoor
Entire stop
releasing control.
High-pressure switch --- The IOL was activated
Outdoor
or an error was detected in the high-pressure
Entire stop
releasing control using the TE.
The power wire may be connected incorrectly.
Outdoor
Check open phase and voltages of the power
Entire stop
supply.
Abnormal temperature was detected by the temp.
Outdoor
Entire stop
sensor of the IGBT heat sink.
Drain pipe, clogging of drainage, float switch
Indoor
circuit, indoor P.C. board --- Drainage is out of
Entire stop
order or the float switch was activated.
Abnormal operation of the indoor fan motor, indoor
Indoor
P.C. board, or indoor DC fan (over current or lock,
Entire stop
etc.) is detected.
There may be gas leakage from the pipe or
Outdoor
Entire stop
connecting part. Check for gas leakage.
4-way valve, indoor temp. sensors (TC/TCJ) --- An
Outdoor
error was detected due to temperature drop of the
Auto-reset
(Indoor)
indoor unit heat exchanger sensor when heating.
Outdoor
High-pressure protection
Entire stop
Outdoor unit fan motor, outdoor unit P.C. board ---
Outdoor
An error (overcurrent, locking, etc.) was detected in
Entire stop
the outdoor unit fan drive circuit.
IGBT, outdoor unit P.C. board, inverter wiring,
compressor --- Short-circuit protection for
Outdoor
Entire stop
compressor drive circuit devices (G-Tr/IGBT) was
activated.
Outdoor unit P.C. board, high-pressure switch ---
Outdoor
Entire stop
Compressor motor position error was detected.
Another indoor unit in the group is raising an alarm. Entire stop
Indoor
E03/L07/L03/L08 alarm check locations and error
Auto-reset
description
� 25 �
Air
status
50-EN