PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. • After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level. • Install the air conditioner securely in a location where the base can sustain the weight adequately. •...
SELECTION OF INSTALLATION When using an air conditioner under low outside temperature condition (Outside temp.:–5°C or lower) with COOL mode, prepare a duct or wind shield so that it is not affected by the wind. <Example> Suction hood (Rear side) Suction Before installation Be careful to the following items before installation.
Installation Place • A place which provides a specified space around the outdoor unit. • A place where the operation noise and discharged air are not given to your neighbors. • A place that is not exposed to a strong wind. •...
Page 8
SELECTION OF INSTALLATION <Obstacle also at the upper side> 1000 or more Obstacles at both front and rear sides Open the upper side and both right and left sides. The height of obstacle at both front and rear side, should be lower than the height of the outdoor unit. <Standard installation>...
Optional Installation Parts (Local Procure) Parts name Refrigerant piping Liquid side : Ø6.4 mm or Ø9.5 mm Gas side : Ø12.7 mm or Ø15.9 mm Pipe insulating material (polyethylene foam, 6 mm thick) Putty, PVC tapes TAKE NOTICE THESE IMPORTANT 4 POINTS BELOW FOR PIPING WORK 1.
Page 10
REFRIGERANT PIPING Tightening of Connecting Part Outer diam. of copper pipe Tightening torque 6.4 mm (diam.) 14 to 18 (1.4 to 1.8 kgf•m) 9.5 mm (diam.) 33 to 42 (3.3 to 4.2 kgf•m) 12.7 mm (diam.) 50 to 62 (5.0 to 6.2 kgf•m) 15.9 mm (diam.) 68 to 82 (6.8 to 8.2 kgf•m) Flare at...
EVACUATING Air Purge This air conditioner can be installed up to the connecting pipe length and height difference in the following table. Max. connecting Capacity rank pipe length (m) SM56 type SM80 type With respect to the preservation of terrestrial environment, adopt “Vacuum pump” for air purge (Evacuate air in the connecting pipes) when installing the unit.
Page 12
EVACUATING Compound pressure gauge Pressure gauge –101kPa (–76cmHg) Handle Lo Charge hose Charge hose (For R410A only) (For R410A only) Vacuum pump Packed valve (Gas side) Service port (Valve core (Setting pin)) *1. Use the vacuum pump, vacuum pump adapters, and gauge manifold referring to the manuals attached to each tool before using them.
ELECTRICAL WORK For the air conditioner that has no power cable, connect a power cable as mentioned below. Model RAV-SM56, RAV-SM80 Power supply Single phase 50 Hz Maximum running current Installation fuse rating 25 A (D type H07 RN-F or 245 IEC 66 Power cable (2.5 mm CAUTION...
FINAL INSTALLATION CHECKS Check and Test Operation For R410A, use the leak detector exclusively manufactured for HFC refrigerant (R410A, R134a, etc.). * The conventional leak detector for HCFC refrigerant (R22, etc.) cannot be used because its sensitivity for HFC refrigerant lowers to approx. 1/40. •...
Recovery method of refrigerant • When recovering refrigerant in case of reinstallation of the indoor or outdoor unit, etc., use the refrigerant recovery switch on the terminal block of the outdoor unit. Work procedure 1. Turn on the power supply. 2.
• Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical parts. Do not store it in a wet basement or expose to rain or water. RAV-SM1101AT-E, RAV-SM1401AT-E ) must be used for the power supply line of this WARNING...
Discharge contact with the cabinet, etc. Addition of refrigerant is unnecessary at the local site. <Addition of refrigerant> Add 40 g of refrigerant for every 1m of pipe which exceeds 20 m. – 18 – RAV-SM1101AT-E, RAV-SM1401AT-E Item...
Page 19
Obstacle at front side wind <Upper side is free> 1. Single unitIn installation 2. Serial installation of two or more units – 19 – RAV-SM1101AT-E, RAV-SM1401AT-E The height of the obstacle should be lower than the height of the outdoor unit. or more...
Page 20
(Open the knockout hole to outside using a screw- 2000 or more or more driver, etc.) – 20 – RAV-SM1101AT-E, RAV-SM1401AT-E Drain hole Drain nipple mounting hole Knockout hole 15 or less Waterproof rubber cap Knockout hole...
After connecting the pipes, be sure to mount the pipe cover. The pipe cover is easily mounted by cutting off the slit at the lower part of the pipe cover. – 21 – RAV-SM1101AT-E, RAV-SM1401AT-E Rear direction Pipe cover Side direction...
R22 to adjust to the specified flare size. The copper 16.6 16.2 pipe gauge is useful for adjusting projection margin 19.7 19.4 size. – 22 – RAV-SM1101AT-E, RAV-SM1401AT-E Electric parts box Service panel Pipe valve fixing plate Wiring hole R410A tool used...
Page 23
Incomplete connections may cause not only a gas leak, but also a trouble of the refrigeration cycle. Do not apply refrigerating machine oil to the flared surface. Cover Piping valve – 23 – RAV-SM1101AT-E, RAV-SM1401AT-E REQUIREMENT NO GOOD Cover...
Close handle Low completely. Turn OFF the vacuum pump. Disconnect the charge hose from the charge port. Tighten valve and caps of the charge port surely. – 24 – RAV-SM1101AT-E, RAV-SM1401AT-E Hexagonal wrench size Outdoor unit at lower side 4 mm...
Page 25
• Securely tighten the cap with a torque wrench. • Cap tightening torque Flare nut Valve size Charge port Push in handle. Flare nut – 25 – RAV-SM1101AT-E, RAV-SM1401AT-E Handle position Handle Closed completely Opened fully Valve handling precautions Ø9.5 33 to 42 N•m (3.3 to 4.2 kgf•m) Ø15.9...
A switch which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring. or more) Earth screw – 26 – RAV-SM1101AT-E, RAV-SM1401AT-E 1 2 3 Earth line Earth line Connecting Power cable cable...
Discharge temp. error ¡ ¡ EEPROM error ¡ ¡ Communication error between IPDU (No abnormal stop) G-Tr short-circuit protection ¥ Detect circuit error ¥ Current sensor error ¥ Comp. lock error ¥ Comp. break down – 27 – RAV-SM1101AT-E, RAV-SM1401AT-E Cause...
Page 28
(7/16 UNF 20 threads per inch) and one for R410A. If the vacuum pump oil (mineral) mixes with R410A a sludge may occur and damage the equipment. Exclusive for HFC refrigerant. – 28 – RAV-SM1101AT-E, RAV-SM1401AT-E Outdoor unit cycle control P.C. board SW802 Refrigerant...
• The capacity saving can be adjusted with three steps, 75%, 50%, and operation stop. Night operation control (Sound reduction) Sound is controlled to 45dB or less in inputting a timer point contact. Compressor operation output The check of the compressor operation time required of a maintenance etc. RAV-SM1101AT-E, RAV-SM1401AT-E – 29 –...
Page 30
4-Way Air Discharge Cassette Type RAV-SP1100UT-E, RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E ACCESSORIES (SOLD SEPARATELY) ... 31 PRECAUTIONS FOR SAFETY ... 31 PARTS NAME ... 33 PARTS NAME OF REMOTE CONTROLLER ... 34 CORRECT USAGE ... 36 AUTOMATIC OPERATION (Auto Changeover) ... 37 Concealed Duct Type RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E ACCESSORIES (SOLD SEPARATELY) ...
ACCESSORIES (SOLD SEPARATELY) Remote controller PRECAUTIONS FOR SAFETY WARNING WARNINGS ABOUT INSTALLATION • Make sure to ask the qualified installation professional in electric work to install the air conditioner. If the air conditioner is inappropriate installed by yourself, it may cause water leak, electric shock, fire, and so on.
Page 32
CAUTION CAUTIONS ABOUT INSTALLATION • Be sure to confirm the following cautions. • Certainly lay the drain hose for perfect draining. Bad drainage may cause flooding in the house and getting furniture wet. • Make sure to connect the air conditioner to an exclusive power supply of the rated voltage, otherwise the unit may break down or cause a fire.
PARTS NAME Indoor unit Button Button to open/close the suction port Air filter Removes dust or trash. (Provided on the suction port.) Outdoor unit Air inlet (Side and rear) Air outlet The image of outdoor unit in the figure is in case Model RAV-SM800AT-E. RAV-SP1100UT-E, RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E Remote controller...
PARTS NAME OF REMOTE CONTROLLER Display section In the display example, all indicators are displayed for the explana- tion. In reality only, the selected contents are indicated. • When turning on the leak breaker at the first time, [SET DATA] flashes on the display part of the remote controller. While this display is flashing, the model is being automatically confirmed.
Page 35
Operation section Push each button to select a desired operation. • The details of the operation needs to be set up once, afterward, the air conditioner can be used by pushing button only. Air volume select button Selects the desired air volume mode. Timer set button TIMER SET button is used when the timer is set up.
CORRECT USAGE When you use the air conditioner for the first time or when you change the SET DATA value, follow the proce- dure below. From the next time, the operation displayed on the remote controller will start by pushing the button only.
AUTOMATIC OPERATION (Auto Changeover) When you set the air conditioner in change, it will automatically select either cooling, heating, or fan only operation depending on the indoor temperature. Start button Push this button to start the air conditioner. Mode select button (MODE) Select Auto.
ADJUSTMENT OF WIND DIRECTIONd • When the air conditioner stops, the flap (adjustment plate of up/down wind direction) directs downward automatically. • When the heating operation is in READY states, the flap (adjustment plate of up/down wind direction) directs upward. The swinging starts after HEAT READY status cleared, SWING controller even if the heating operation is in READY status.
TIMER OPERATION A type of timer operation can be selected from the following three types. OFF timer : The operation stops when the time of timer has reached the set time. Repeat OFF timer : Every time, the operation stops after the set time has passed. ON timer : The operation starts when the time of timer has reached the set time.
HINTS FOR ECONOMICAL OPERATION Maintain room temperature at comfortable level Clean air filters The clogged air filter impairs the performance of the air conditioner. Never open doors and windows more often than necessary To keep cool or warm air in the room, never open doors and windows more often than necessary. Window curtains In cooling, close the curtains to avoid direct sunlight.
MAINTENANCE Cleaning of remote controller CAUTION • Use a dry cloth to wipe the remote controller. • A cloth dampened with cold water may be used on the indoor unit if it is very dirty. • Never use a damp cloth on the remote controller. •...
Page 42
AIR CONDITIONER OPERATIONS AND PERFORMANCE 3 minutes protection function 3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main power switch/circuit breaker is turned on for re-starting the air conditioner. Power failure Power failure during operation will stop the unit completely. •...
RE-INSTALLATION DANGER Ask the dealer or an installation professional to re-install the air conditioner to a new place or move it to another place and to observe the following items. If the air conditioner is inappropriate installed by yourself, it may cause electric shock or fire. Do not install the air conditioner in the following places •...
Page 44
Before you ask for servicing or repairs, check the following points. Inoperative • The main power switch is turned off. • The circuit breaker is activated to cut off power supply. • The main power fuse has blown out. • Stoppage of electric current. Does not cool well or heat well •...
ACCESSORIES (SOLD SEPARATELY) Remote controller PRECAUTIONS FOR SAFETY WARNING WARNINGS ABOUT INSTALLATION • Make sure to ask the qualified installation professional in electric work to install the air conditioner. If the air conditioner is inappropriate installed by yourself, it may cause water leak, electric shock, fire, and so on.
Page 46
CAUTION CAUTIONS ABOUT INSTALLATION • Be sure to confirm the following cautions. • Certainly lay the drain hose for perfect draining. Bad drainage may cause flooding in the house and getting furniture wet. • Make sure to connect the air conditioner to an exclusive power supply of the rated voltage, otherwise the unit may break down or cause a fire.
PARTS NAME Indoor unit Supply air grille Supply air chamber Outdoor unit Air inlet (Side and rear) Air outlet RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E Remote controller – 47 – NOTE : Parts marked with indicate the locally procured parts. Connecting duct Indoor unit Duct flange Air filter...
PARTS NAME OF REMOTE CONTROLLER Display section All display items are shown in right figure for the explanation. Only selected contents are displayed in actual operation. • When turning on the leakage breaker at the first time, [SET DATA] flashes on the display part of the remote controller. While this display is flashing, the model is being automatically confirmed.
Page 49
Operation section Push each button to select a desired operation. • The details of the operation needs to be set up once, the same states are used by pushing button. Fan mode button Selects a fan mode. Timer set button TIMER SET button is used when the timer is set up.
CORRECT USAGE When you use the air conditioner for the first time or when you change SET DATA value, follow the procedure below. From the next time, the operation will start as set state by pushing the Preparation Turn on the main power switch and/or the leakage breaker. •...
AUTOMATIC OPERATION (Auto Changeover) When you set the air conditioner in either cooling, heating, or fan only operation depending on the indoor room temperature. Start button Push this button to start the air conditioner. Mode select button (MODE) Select Auto. Temperature button Set the desired temperature.
TIMER OPERATION A type of timer operation can be selected from the following three types. OFF timer : The operation stops after the set time has passed. Repeat OFF timer : Every time, the operation stops after the set time has passed. ON timer : The operation starts after the set time has passed.
Page 53
HINTS FOR ECONOMICAL OPERATION Maintain room temperature at comfortable level Clean air filters Airflow and performance are reduced if the air filters become blocked. Do not open doors and windows more often than necessary To keep cool or warm air in the room, do not open doors and windows more often than necessary. Window curtains In cooling, close the curtains to avoid direct sunlight.
MAINTENANCE Cleaning of remote controller CAUTION • Use a dry cloth to wipe the remote controller. • A cloth dampened with cold water may be used on the indoor unit if it is very dirty. • Never use a damp cloth on the remote controller. •...
AIR CONDITIONER OPERATIONS AND PERFORMANCE 3 minutes protection function 3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main power switch/circuit breaker is turned on for re-starting the air conditioner. Power failure Power failure during operation will stop the unit completely. •...
RE-INSTALLATION DANGER Ask the dealer or an installation professional to re-install the air conditioner to a new place or move it to another place and to observe the following items. If the air conditioner is inappropriate installed by yourself, it may cause electric shock or fire. Do not install the air conditioner in the following places •...
Page 57
Before you ask for servicing or repairs, check the following points. Inoperative • The main power switch is turned off. • The circuit breaker is activated to cut off power supply. • The main power fuse has blown out. • Stoppage of electric current. Does not cool well or heat well •...
TROUBLES AND CAUSES (Concerning Remote Controller) Before you ask for servicing or repairs, check the following points: Symptoms The fan speed can not be • Check whether the MODE indi- changed. cated on the display is “AUTO”. • Check whether the MODE indi- cated on the display is “DRY”.
ACCESSORIES (SOLD SEPARATELY) Remote controller PRECAUTIONS FOR SAFETY WARNING WARNINGS ABOUT INSTALLATION • Make sure to ask the qualified installation professional in electric work to install the air conditioner. If the air conditioner is inappropriate installed by yourself, it may cause water leak, electric shock, fire, and so on.
CAUTION CAUTIONS ABOUT INSTALLATION • Be sure to confirm the following cautions. • Certainly lay the drain hose for perfect draining. Bad drainage may cause flooding in the house and getting furniture wet. • Make sure to connect the air conditioner to an exclusive power supply of the rated voltage, otherwise the unit may break down or cause a fire.
PARTS NAME Indoor unit Button Button to open/close the suction port Air filter Removes dust or trash. (Provided on the suction port.) Outdoor unit Air inlet (Side and rear) Air outlet The image of outdoor unit in the figure is in case Model RAV-SM800AT-E. RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E Remote controller –...
PARTS NAME OF REMOTE CONTROLLER Display section In the display example, all indicators are displayed for the explana- tion. In reality only, the selected contents are indicated. • When turning on the leak breaker at the first time, [SET DATA] flashes on the display part of the remote controller. While this display is flashing, the model is being automatically confirmed.
Page 63
Operation section Push each button to select a desired operation. • The details of the operation needs to be set up once, afterward, the air conditioner can be used by pushing button only. Air volume select button Selects the desired air volume mode. Timer set button TIMER SET button is used when the timer is set up.
CORRECT USAGE When you use the air conditioner for the first time or when you change the SET DATA value, follow the proce- dure below. From the next time, the operation displayed on the remote controller will start by pushing the button only.
AUTOMATIC OPERATION (Auto Changeover) When you set the air conditioner in change, it will automatically select either cooling, heating, or fan only operation depending on the indoor temperature. Start button Push this button to start the air conditioner. Mode select button (MODE) Select Auto.
ADJUSTMENT OF WIND DIRECTION • When the air conditioner stops, the flap (adjustment plate of up/down wind direction) directs downward automatically. • When the heating operation is in READY states, the flap (adjustment plate of up/down wind direction) directs upward. The swinging starts after HEAT READY status cleared, SWING controller even if the heating operation is in READY status.
TIMER OPERATION A type of timer operation can be selected from the following three types. OFF timer : The operation stops when the time of timer has reached the set time. Repeat OFF timer : Every time, the operation stops after the set time has passed. ON timer : The operation starts when the time of timer has reached the set time.
Page 68
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E HINTS FOR ECONOMICAL OPERATION Maintain room temperature at comfortable level Clean air filters The clogged air filter impairs the performance of the air conditioner. Never open doors and windows more often than necessary To keep cool or warm air in the room, never open doors and windows more often than necessary. Window curtains In cooling, close the curtains to avoid direct sunlight.
MAINTENANCE Cleaning of remote controller CAUTION • Use a dry cloth to wipe the remote controller. • A cloth dampened with cold water may be used on the indoor unit if it is very dirty. • Never use a damp cloth on the remote controller. •...
AIR CONDITIONER OPERATIONS AND PERFORMANCE 3 minutes protection function 3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main power switch/circuit breaker is turned on for re-starting the air conditioner. Power failure Power failure during operation will stop the unit completely. •...
RE-INSTALLATION DANGER Ask the dealer or an installation professional to re-install the air conditioner to a new place or move it to another place and to observe the following items. If the air conditioner is inappropriate installed by yourself, it may cause electric shock or fire. Do not install the air conditioner in the following places •...
Page 72
Before you ask for servicing or repairs, check the following points. Inoperative • The main power switch is turned off. • The circuit breaker is activated to cut off power supply. • The main power fuse has blown out. • Stoppage of electric current. Does not cool well or heat well •...
Page 73
4-Way Air Discharge Cassette Type RAV-SP1100UT-E, RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E Accessory parts and Parts to be procured locally ... 74 PRECAUTIONS FOR SAFETY ... 75 SELECTION OF INSTALLATION PLACE ... 77 DRAIN PIPING WORK ... 82 REFRIGERANT PIPING AND EVACUATING ... 84 Concealed Duct Type RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E Accessory parts and Parts to be procured locally ...
Accessory parts and Parts to be procured locally H Accessory parts Part name Q’ty Shape Installation This (Be sure to hand over to customers) Manual manual Heat insulating For heat insulation of pipe pipe connecting section Installation For confirmation of ceiling opening ——...
PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. • After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
Page 76
PRECAUTIONS FOR SAFETY • After unpacking the unit, examine it carefully if there are possible damage. • Do not install in a place that might increase the vibration of the unit. • To avoid personal injury (with sharp edges), be careful when handling parts. •...
SELECTION OF INSTALLATION PLACE • Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. • Install the air conditioner at a height 2.5m or more from the floor. If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you may contact with revolving fan or active electricity.
Page 78
SELECTION OF INSTALLATION PLACE Selection of installation place In case of continued operation of the indoor unit under high-humidity conditions as described below, dew may condense and water may drop. Especially, high-humidity atmosphere (dew point temperature : 23°C or more) may generate dew inside the ceiling.
External view Strictly comply with the following rules to prevent damage of the indoor units and human injury. • Do not put a heavy article on the indoor unit. (Even units are packaged) • Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc.
Page 80
SELECTION OF INSTALLATION PLACE Opening a ceiling and installation of hanging bolts <Treatment of ceiling> The ceiling differs according to structure of building. For details, consult your constructor or interior finish contractor. In the process after the ceiling board has been removed, it is important to reinforce ceiling foundation (frame) and to keep horizontal level of installed ceiling correctly in order to prevent vibration of ceiling board.
Page 81
REQUIREMENT Before installation of the indoor unit, be sure to remove the cushion for transportation between the fan and the bell mouth. Running the unit without removing the cushion may damage the fan motor. Be sure to remove the cushion for transportation between the fan and the bell mouth.
DRAIN PIPING WORK CAUTION • Following the Installation Manual, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew. Inappropriate piping work may result in water leakage in the room and wet of furniture.
Page 83
Connection procedure Connect a socket and a hard vinyl chloride pipe. • Using adhesive agent for vinyl chloride pipe, connect the drain pipes certainly so that water does not leak. • It takes approx. 10 hours to dry and harden the adhesive agent.
REFRIGERANT PIPING AND EVACUATING Refrigerant Piping 1. If the outdoor units are to be mounted on a wall, make sure that the supporting platform is sufficiently strong. The platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient consideration should be given to ensuring that the outdoor unit will not fall.
Page 85
Piping with outdoor unit • Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit. Air purge Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit. For details, follow to the Installation Manual attached to the outdoor unit.
ELECTRICAL WORK 1. Using the specified cables, ensure to connect the wires, and fix wires securely so that the external tension to the cables do not affect the connecting part of the terminals. Incomplete connection or fixation may cause a fire, etc. 2.
Page 87
Cable connection • Be sure to connect the cables matching the terminal numbers. Incorrect connection causes a trouble. • Be sure to pass the cables through the bushing of cabling connection port of the indoor unit. • Keep a margin (Approx. 100mm) on a cable to hang down the electric parts box at servicing, etc. •...
ELECTRICAL WORK Cabling 1. Remove a screw and then remove cover of the electric parts box. 2. Strip wire ends (10 mm). 3. Match wire colors with terminal numbers on indoor and outdoor units’ terminal blocks and firmly screw wires to the corresponding terminals. 4.
TEST RUN Before test run • Before turning on the power supply, carry out the following procedure. 1) Using 500V-megger, check 1M or more exists between the terminal block 1 to 3 and the earth. If 1M or less is detected, do not run the unit. Do not apply to the remote controller circuit. 2) Check the valve of the outdoor unit being opened fully.
TROUBLESHOOTING Confirmation and check When a trouble occurred in the air conditioner, the check code and the indoor unit No. appear on the display part of the remote controller. The check code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following “Confirmation of error history”...
MAINTENANCE Before maintenance, be sure to turn off the leakage breaker. Cleaning of air filter • If is displayed on the remote controller, maintain the air filter. • Clogging of the air filter reduce cooling/heating performance. Cleaning of panel and air filter Preparation : 1.
Accessory parts and Parts to be procured locally r Accessory parts Part name Q’ty Pipe insulator 561BT Clamp for air 801BT filter fixing 1101BT 1401BT Washer for unit hung-up <Separate sold parts> Part name Q’ty Standard wired remote controller r Parts to be procured locally Connecting pipe (Liquid side) (6.4mm (diam.), Nominal (diam.) 1/4”...
PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. • After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
Page 94
PRECAUTIONS FOR SAFETY • After unpacking the unit, examine it carefully if there are possible damage. • Do not install in a place that might increase the vibration of the unit. • To avoid personal injury (with sharp edges), be careful when handling parts. •...
SELECTION OF INSTALLATION PLACE • Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. • Install the air conditioner at a height 2.5m or more from the floor. If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you may contact with revolving fan or active electricity.
INSTALLATION OF INDOOR UNIT Install the air conditioner certainly at a place to sufficiently withstand the weight. If the strength is insufficient, the unit may fall down resulting in human injury. Perform a specified installation work to guard against an earthquake. An incomplete installation can cause accidents by the units falling and dropping.
Page 97
External view The hanging bolt pitch on horizontal direction (B) is not halved at center with the ceiling opening size. Therefore, check the relational position in the following figure. Knock-out hole Ø125 (Air take-in port) 6-Ø4 Tapping screw undersized hole Ø160 Suction port canvas (Separate sold)
Page 98
INSTALLATION OF INDOOR UNIT 1. Hanging down of indoor unit Refer to installation figures of hanging material and hanging bolt. • Adjustment of hanging bolt length and nut position Adjust hanging bolt length and nut position as shown in the figure before hanging down the indoor unit.
Concealed duct type NOTE: • Recommended supplying grille size 400 cm² each or more Ledge ceiling concealed duct type Quality of supplying grilles SM561BT SM801BT SM1101BT SM1401BT Restriction to installation 1. Installation clearance • As shown in the figure, keep clearance around the indoor unit. Inner ceiling 100mm or more RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E...
AIR DUCTING WORK Static pressure characteristics of each model Fig. 1 RAV-SM561BT (Round duct) Standard air volume 780m³/h Air volume m³/h Fig. 2 RAV-SM561BT (Square duct) Standard air volume 780m³/h Air volume m³/h RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E Fig. 3 RAV-SM801BT (Round duct) Fig.
Page 101
Fig. 5 RAV-SM1101BT (Round duct) Standard air volume 1620m³/h 1620 1200 Air volume m³/h Fig. 6 RAV-SM1101BT (Square duct) Standard air volume 1620m³/h 1620 1200 Air volume m³/h RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E Fig. 7 RAV-SM1401BT (Round duct) 2000 1200 Fig. 8 RAV-SM1401BT (Square duct) 2000 1200 –...
Page 102
AIR DUCTING WORK Installation reference The air supply ducting work is classified in two ways, one is branched by the round ducts, and the other is branched by the square ducts. (Be sure to divide the air supply duct into three or more branches.) <Round duct>...
Page 103
Connecting method of the duct 1. Supply air side <Round duct> 1. Make the round duct according to inner dimension of the flange Use a glass wool board with inside/outside finishing 25mm-thickness and 24kg/m³-density. 2. Connect the flange and each type of duct. (Fig. 1) Thermal insulator (50mm (w), 6mm (t)) Aluminum tape (50mm-width)
Page 104
AIR DUCTING WORK Hanging of indoor unit Lift up the unit with a lifter, etc., and set the hanging metal in the hanging bolt. • Hook nut of the hanging bolt to the groove of the hanging metal on the main unit. •...
DRAIN PIPING WORK Piping material • For laying pipes underground, use hard vinyl chloride pipe. VP25 (Inner diamater Ø32mm) Piping and cautions • Set drain side of pipe at downward slope. (1/100 or more) • Be sure to apply thermal insulation (foaming polyethylene, 10mm-thickness or more) for pipes passing through the room.
Page 106
DRAIN PIPING WORK Drain-up If down-slope cannot be set on a drain pipe, drain-up is possible. • Set the height of drain pipe 550mm or less from the bottom face of the indoor unit. • Pull out the drain pipe from connecting port of the drain pipe of the indoor unit by 100mm or shorter, and stand up it vertically.
REFRIGERANT PIPING AND EVACUATING Refrigerant piping 1. If the outdoor units are to be mounted on a wall, make sure that the supporting platform is sufficiently strong. The platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient consideration should be given to ensuring that the outdoor unit will not fall.
Page 108
REFRIGERANT PIPING AND EVACUATING Piping with outdoor unit • Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit. Air purge Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit.
ELECTRICAL WORK NOTE: For selection and connection method of the power supply cords, refer to the details in the Installation Manual of the outdoor unit. • Be sure connect earth wire. Do not connect the earth wire to gas pipe, pipe of water supply, lightning conductor, and earth wire of telephone.
Page 110
ELECTRICAL WORK Cabling 1. As shown in the figure, remove a screw then remove cover of the electric part. 2. Strip wire ends (10 mm). 3. Match wire colors with terminal numbers on indoor and outdoor units’ terminal blocks and firmly screw wires to the corresponding terminals.
TEST RUN Before test run • Before turning on the power supply, carry out the following procedure. 1) Using 500V-megger, check 1M or more exists between the terminal block 1 to 3 and the earth. If 1M or less is detected, do not run the unit. Do not apply to the remote controller circuit. 2) Check the valve of the outdoor unit being opened fully.
TROUBLESHOOTING Confirmation and check When a trouble occurred in the air conditioner, the check code and the indoor unit No. appear on the display part of the remote controller. The check code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following “Confirmation of error history”...
APPLICABLE CONTROLS When using the equipment at the first time, it will take a lot of time that the remote controller accepts an operation after power was on. However, it is not a trouble. • Automatic address • While automatic addressing, the operation cannot be performed on the remote controller. •...
Page 114
APPLICABLE CONTROLS Setup of external static pressure Matching with the resistance (External static pressure) of the duct to be connected, be sure to set up the tap exchange according to the basic operation procedure • For the item code in Procedure •...
Page 115
Change of lighting time of filter sign According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed. Follow to the basic operation procedure • For the item code in Procedure • For the set data in Procedure data of lighting time of filter sign to be changed from the table below.
INSTALLATION/SERVICING TOOLS Tools Tools Applicable to R22 model Gauge manifold Charge hose ¡ Electronic balance for refrigerant charging Torque wrench (nominal diam. 1/4, 3/8, 1/2, 5/8) ¡ : Newly prepared (They are special requirements for R407C, separate from those for R22.) : Existing tools are available.
Accessory parts and Parts to be procured locally r Accessory parts Part name Q’ty Shape Owner’s Man — Installation Manual This manual Installation pattern — Thermal insulation pipe Washer M10 × Ø25 Hose band <Separate sold parts> Part name Q’ty Shape Standard wired remote controller...
PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. • After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
Page 119
• After unpacking the unit, examine it carefully if there are possible damage. • Do not install in a place that might increase the vibration of the unit. • To avoid personal injury (with sharp edges), be careful when handling parts. •...
SELECTION OF INSTALLATION PLACE • Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. • Perform a specified installation work to guard against an earth quake. An incomplete installation can cause accidents by the units failing and dropping.
Height of ceiling Set the installable height of the ceiling within 4m, otherwise the air distribution will become poor. If height of ceiling exceeds 3.5m, hot air becomes difficult to reach the floor surface, and then the change of setup of high ceiling is necessary. When incorporating a filter sold separately, the change of setup of high ceiling is also necessary.
Page 122
SELECTION OF INSTALLATION PLACE External view Strictly comply with the following rules to prevent damage of the indoor units and human injury. • Do not put a heavy article on the indoor unit. (Even units are packaged) • Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc.
Page 123
Installation of hanging bolts Use M10 hanging bolts (4 pcs, to be local procure). Matching to the existing structure, set pitch according to size in the unit external view as shown below. New concrete slab Install the bolts with insert brackets or anchor bolts. (Blade type (Slide type (Pipe hanging...
SELECTION OF INSTALLATION PLACE Installation of indoor unit • Preparation before holding down main unit * Confirm the presence of the ceiling material beforehand because the fixing method of hanging metal when the ceiling material is set differs from that when the ceiling material is not set. <There is ceiling material>...
DRAIN PIPING WORK CAUTION • Following the Installation Manual, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew. Inappropriate piping work may result in water leakage in the room and wet of furniture.
Page 126
DRAIN PIPING WORK Connection of drain hose • Insert the attached drain hose into the drain pipe connecting port on the drain pan up to the end. • Fit the attached hose band to the end of the pipe connecting port, and then tighten it securely. REQUIREMENT •...
REFRIGERANT PIPING AND EVACUATING Refrigerant Piping • The connecting sections of the refrigerant pipes are provided at the positions in the figure below. * When using the drain up kit sold Rear side Upper side separately, the pipe can be drawn out only from the upper side.
Page 128
REFRIGERANT PIPING AND EVACUATING Piping with outdoor unit • Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit. Air purge Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit.
ELECTRICAL WORK 1. Using the specified cables, ensure to connect the wires, and fix wires securely so that the external tension to the cables do not affect the connecting part of the terminals. Incomplete connection or fixation may cause a fire, etc. 2.
Page 130
ELECTRICAL WORK Cable connection • Be sure to connect the cables matching the terminal numbers. Incorrect connection causes a trouble. • Be sure to pass the cables through the bushing of cabling connection port of the indoor unit. • Keep a margin (Approx. 100mm) on a cable to hang down the electric parts box at servicing, etc. •...
Page 131
Cabling 1. Remove a screw and then remove cover of the electric parts box. 2. Strip wire ends (10 mm). 3. Match wire colors with terminal numbers on indoor and outdoor units’ terminal blocks and firmly screw wires to the corresponding terminals. 4.
TEST RUN Before test run • Before turning on the power supply, carry out the following procedure. 1) Using 500V-megger, check 1M or more exists between the terminal block 1 to 3 and the earth. If 1M or less is detected, do not run the unit. Do not apply to the remote controller circuit. 2) Check the valve of the outdoor unit being opened fully.
TROUBLESHOOTING Confirmation and check When a trouble occurred in the air conditioner, the check code and the indoor unit No. appear on the display part of the remote controller. The check code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following “Confirmation of error history”...
APPLICABLE CONTROLS When using the equipment at the first time, it will take a lot of time that the remote controller accepts an operation after power was on. However, it is not a trouble. • Automatic address • While automatic addressing, the operation cannot be performed on the remote controller. •...
Page 135
In case of installation to high ceiling When the height of the ceiling to be installed exceeds 3.5m, adjustment of air volume is necessary. Set up the high ceiling. • Set according to the basic operation procedure • Item code in Procedure specifies [5d]. •...
Page 136
APPLICABLE CONTROLS Change of lighting time of filter sign According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed. Follow to the basic operation procedure • For the item code in Procedure •...
INSTALLATION/SERVICING TOOLS Tools Tools Applicable to R22 model Gauge manifold Charge hose ¡ Electronic balance for refrigerant charging Torque wrench (nominal diam. 1/4, 3/8, 1/2, 5/8) ¡ : Newly prepared (They are special requirements for R407C, separate from those for R22.) : Existing tools are available.
Page 138
MAINTENANCE Cleaning of air filter • [FILTER] is displayed on the remote controller, maintain the air filter. • Clogging of the air filter decreases the cooling/heating effect. UNIT • After cleaning, push [ [FILTER] display disappears. Open the suction grille •...