Test Run - Toshiba RAV-SM182CTP-UL Installation Manual

Hide thumbs Also See for RAV-SM182CTP-UL:
Table of Contents

Advertisement

7
After check of the changed contents, Push
the "
No" [
F2] button to
finish the setting operation. "
Setting"
appears on the screen for a while, then the
screen returns to the "Field setting menu"
screen.
Pushing the "
No" [
F2] button
displays the unit selection screen when the
group control is used. Push the [
CANCEL]
button on the unit selection screen to finish
the setting operation. "
Setting" appears on
the screen for a while, then the screen returns
to the "Field setting menu" screen.
41-EN
 46 °F (8 °C) operation
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
1
Push the [
MENU] button to display the
menu screen.
Push and hold the [
MENU] button and
the [
˅ ] button at the same time to
display the "Field setting menu".
Push and hold the buttons for more than 4
seconds.
Push the [
˄ ] / [
˅ ] button to select
"DN setting" on the "Field setting menu"
screen, then push the "
Set"
[
F2] button.
The fan and louver of the indoor unit operate.
When the group control is used, the fan and
louver of the selected indoor unit operate.
Specify CODE No. [D1]
Move the cursor to select "Code(DN)" with the
"
˂ " [
F1] button, then set
"Code(DN)" with the [
˄ ] / [
˅ ]button.
Move the cursor to select "Data" with the
"
>" [
F2] button, then set "Data"
with the [
˄ ] / [
˅] button.
SET DATA
46 °F (8 °C) Operation setting
None
0000
(Factory default)
0001
46 °F (8 °C) Operation setting
Push the [
CANCEL] button to return.
� 21 �
9

Test run

 Before test run
• Before turning on the power supply, carry out the
following procedure.
1) By using 500 V-megger, check that resistanceof
1MΩ or more exists between the terminal block
1 to 3 and the earth (grounding).
If resistance of less than 1MΩ is detected, do not
run the unit.
2) Check the valve of the outdoor unit being opened
fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
 Execute a test run
Operate the unit with the wired remote controller as
usual.
For the procedure of the operation, refer to the
attached Owner's Manual.
A forced test run can be executed in the following
procedure even if the operation stops by
thermostat-OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than
the test run because it applies an excessive load to
the devices.
1
Push the [
MENU] button to display the
menu screen.
Push and hold the [
MENU] button and
the [
˅ ] button at the same time to
display the "Field setting menu".
Push and hold the buttons for more than 4
seconds.
Item
Function
Settings for when performing
1. Test mode
the test operation after
installation
Registration of information
about the contact number for
2. Register service info
service, model name and
serial number of the indoor unit
and outdoor unit
List of latest 10 alarm data:
3. Alarm history
information of check code, date,
time, and unit
Monitoring data of sensor
4. Monitor function
temperature, rotating speed of
the compressor or other factor.
Change the louver indication
5. Setting louver
setting to match the indoor unit
position
type.
Set whether or not the
6. Setting timer
operation mode can be selected
operation mode
when setting the schedule timer.
Advanced settings using
7. DN setting
DN code
Push the [
CANCEL] button to return.
42-EN