20.2 To route and fix the transmission wiring

REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
Model
REYA10
REYA13
REYA16
REYA18
REYA20
REYA22
REYA24
REYA26
REYA28
For all models:
Phase and frequency: 3N~ 50 Hz
Voltage: 380~415 V
For non-standard combinations
Calculate the recommended fuse capacity.
Formula
Calculate, by adding the minimum circuit amps of each used unit
(according to the table above), multiply the result by 1.1 and
select the next higher recommended fuse capacity.
Example
Combining the REYA24 by using the REYA10 and REYA14.
Minimum circuit ampacity of the REYA10=22.0 A
Minimum circuit ampacity of the REYA14=27.0 A
Accordingly, the minimum circuit ampacity of the
REYA24=22.0+27.0=49.0 A
Multiply the above result by 1.1: (49.0 A×1.1)=53.9 A, so the
recommended fuse capacity would be 63 A.
NOTICE
When using residual current operated circuit breakers, be sure to use a high-speed
type 300 mA rated residual operating current.
NOTICE
Sheathed and shielded cables are required for transmission wiring between outdoor
unit and BS unit.
Transmission wiring can be routed through the front side only. Fix it to the upper
mounting hole.
Multi outdoor units
Minimum circuit ampacity
30.0 A
31.1 A
32.2 A
38.1 A
40.1 A
46.0 A
47.1 A
51.0 A
55.0 A
20
Electrical installation
|
Recommended fuses
40 A
40 A
40 A
50 A
50 A
63 A
63 A
63 A
63 A
Installer and user reference guide
121