Using The Leak Detection Function; About Automatic Leak Detection - Daikin VRV 5 REYA8A7Y1B Installer And User Manual

Table of Contents

Advertisement

21.3 Using the leak detection function

21.3.1 About automatic leak detection

REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
E Load factor
F Outside air temperature
T
Condensing temperature
c
Quick
Powerful
Mild
Room temperature evolution:
A
F
E
B
A Indoor unit set temperature
B Operation start
C Operating time
D Mild
E Quick
F Powerful
The (automatic) leak detection function is not by default activated and can only
start working when the additional refrigerant charge is inputted into the system's
logic (see [2‑14]).
The leak detection operation can be automated. By changing parameter [2‑88] to
chosen value, the interval time or the time until the next automatic leak detection
operation can be chosen. The parameter [2‑88] defines whether the leak detection
operation is executed one time (within [2‑65] days) or intermittent, respecting an
interval of [2‑65] days.
Availability of the leak detection function feature requires input of the additional
refrigerant charge amount immediately after finishing the charging. The input must
be executed before performing the test operation.
NOTICE
If a wrong value is input for the additional charged refrigerant weight, the accuracy
of the leak detection function will decrease.
INFORMATION
The weighed and already recorded amount of additional refrigerant charge (not
the total amount of refrigerant present in the system) must be entered.
When the height difference between indoor units is ≥50/40 m, the leak detection
function can not be used.
D
21
Configuration
|
C
Installer and user reference guide
147

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents