Daikin Altherma 3 R ECH2O Installer's Reference Manual page 309

Hide thumbs Also See for Altherma 3 R ECH2O:
Table of Contents

Advertisement

8/13
Field settings table
Breadcrumb
Field code
Setting name
9.C.2
[7-05]
Boiler efficiency
9.C.3
[C-03]
Temperature
9.C.4
[C-04]
Hysteresis
Installer settings
9.D
[C-09]
Alarm output
9.E
[3-00]
Auto restart
9.F
[E-08]
Power saving function
9.G
Disable protections
└─ Overview field settings
9.I
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
9.I
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
9.I
[0-02]
High ambient temp. for LWT add zone heating WD curve.
9.I
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
9.I
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
9.I
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
9.I
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
9.I
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
9.I
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
9.I
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
9.I
[0-0D]
High ambient temp. for DHW WD curve.
9.I
[0-0E]
Low ambient temp. for DHW WD curve.
9.I
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
9.I
[1-01]
High ambient temp. for LWT main zone heating WD curve.
9.I
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
9.I
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
9.I
[1-04]
Weather dependent cooling of the main leaving water temperature zone.
9.I
[1-05]
Weather dependent cooling of the additional leaving water temperature zone
9.I
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
9.I
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
9.I
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
9.I
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
9.I
[1-0A]
What is the averaging time for the outdoor temp?
4P670988-1A - 2022.02
Range, step
Default value
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step 1°C
3°C
R/W
0: Normally open
1: Normally closed
R/W
0: No
1: Yes
R/W
0: disabled
1: Enabled
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
25°C
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0:
40°C
[2-0C]=1:
45°C
[2-0C]=2:
55°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0:
18°C
[2-0C]=1:
5°C
[2-0C]=2:
18°C
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
Min(45~[6-0E])~[6-0E]°C, step: 1°C
55°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0:
40°C
[2-0C]=1:
45°C
[2-0C]=2:
55°C
R/W
[9-01]~min(45, [9-00])°C, step: 1°C
[2-0C]=0:
25°C
[2-0C]=1:
25°C
[2-0C]=2:
25°C
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
[2-0C]=0:
18°C
[2-0C]=1:
5°C
[2-0C]=2:
18°C
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
(*6) EKECBUA3V_(*7) EKECBUA6V_(*8) EKECBUA9W_(*9) BUH less_
Installer setting at variance with
default value
Date
Value
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*10) 11P_(*11) 16P