11
|
Configuration
Emergency
Installer reference guide
224
Operation
#
Code
[9.3.8]
[4‑00]
INFORMATION
When heating of the DHW by the heat pump is too slow, it may affect a comfortable
operation of the space heating/cooling circuit. If so, allow the backup heater to assist
during DHW operation by setting [4-00]=1 or 2.
INFORMATION
If backup heater operation during space heating needs to be limited but can be
allowed for domestic hot water operation, then set [4‑00] to 2.
Emergency
When the heat pump fails to operate, the backup heater or boiler can serve as an
emergency heater. It then takes over the heat load either automatically or by
manual interaction.
When Emergency is set to Automatic and a heat pump failure occurs, the
backup heater or boiler automatically takes over the domestic hot water
production and space heating.
When Emergency is set to Manual and a heat pump failure occurs, the
domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the Malfunctioning main
menu screen and confirm whether the backup heater can take over the heat load
or not.
Alternatively, when Emergency is set to:
-
auto SH reduced/DHW on, space heating is reduced but domestic hot
water is still available.
-
auto SH reduced/DHW off, space heating is reduced and domestic hot
water is NOT available.
-
auto
SH
normal/DHW
domestic hot water is NOT available.
Similarly as in Manual mode, the unit can take the full load with the backup
heater or boiler if the user activates this via the Malfunctioning main menu
screen.
To keep energy consumption low, we recommend to set Emergency to auto SH
reduced/DHW off if the house is unattended for longer periods.
Description
Backup heater operation:
0: Restricted
1: Allowed
2: Only
DHW: Backup heater operation is
enabled for domestic hot water and disabled
for space heating.
off, space heating operates as normally but
ERLA11~16DAV3+W1 + EBSH/X(B)11+16P30+50DF
Daikin Altherma 3 R ECH₂O
4P663482-1B – 2022.07