11
|
Configuration
Installer reference guide
202
#
Code
[4.4]
[7‑02]
[4.4]
[7‑02]
NOTICE
NOT configuring the system in the following way can cause damage to the heat
emitters. If there are 2 zones, it is important that in heating:
▪
the zone with the lowest water temperature is configured as the main zone, and
▪
the zone with the highest water temperature is configured as the additional zone.
NOTICE
If there are 2 zones and the emitter types are wrongly configured, water of high
temperature can be sent towards a low temperature emitter (underfloor heating). To
avoid this:
▪
Install an aquastat/thermostatic valve to avoid too high temperatures towards a
low temperature emitter.
▪
Make sure you set the emitter types for the main zone [2.7] and for the
additional zone [3.7] correctly in accordance with the connected emitter.
Description
▪
0: Single zone
Only one leaving water temperature zone:
a Main LWT zone
▪
1: Dual zone
Two leaving water temperature zones. The
main leaving water temperature zone consists
of the higher load heat emitters and a mixing
station to achieve the desired leaving water
temperature. In heating:
c
a Additional LWT zone: Highest temperature
b Main LWT zone: Lowest temperature
c Mixing station
ERLA11~16DAV3+W1 + EBSH/X(B)11+16P30+50DF
a
a
b
Daikin Altherma 3 R ECH₂O