Connection Diagrams; Monitored Function; Switching Value Adjusting - Wieland SVM 4001K-A Operating Instruction

Standstill monitoring for 1- and 3-phases motor without sensor system
Hide thumbs Also See for SVM 4001K-A:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 5
Operating instruction (translation from original)
SVM 4001K-A / 4001K-C
Standstill monitoring for 1- and 3-phases motor without sensor system

3 Connection diagrams

Diagram 1a:
Delta-connection
3-phases motor
Diagram 1b:
Star connection
3-phases motor
Diagram 1c:
Star delta-connection
3-phases moto
Diagram 1d:
connection
1-phases motor

7 Switching value adjusting

Connect the device to the operating voltage.
Hold the SET key for approx. 3 s until all LEDs flash red.
After pressing the key, the LEDs flash red according to the binary combination of the
current parameter level (see table 2).
Briefly pressing the SET key assigns the next level in the sequence.
Pressing the SET key for approx. 2 s permanently saves the new value and exits setting
mode.
Table 2
Position
1
Value
LED: b8 / OK
adjustment
LED: b4 / STOP
b2
b1
Contacts on
[mV]
50
Contacts out
[mV]
120
8 Setting the on delay time for output contacts
Connect the device to the operating voltage.
Hold the SET key for approx. 6 s until all LEDs flash green.
After pressing the key, the LEDs flash according to the binary combination of the current
parameter level (see table 3). Every short press increases the value by one level.
Pressing the key for approx. 2 s saves the new value.
Pressing the key for ≥ 20 s ends the setting mode and restores the previous values.
Table 3
Position
1
Time adjustment
LED: b8 / OK
LED: b4/STOP
b2
b1
[s]
Time delay
0.5
Doc. # BA000926 – 06/2022 (Rev. E)
2
3
4
5
55
60
65
70
120
120
120
120
2
3
4
5
1
2
3
4
SVM 4001K-A / 4001K-C
Wieland Electric GmbH
Brennerstraße 10 – 14
96052 Bamberg
Phone +49 951 9324-0
Fax
+49 951 9324-198
info@wieland-electric.com
www.wieland-electric.com
4 Display
After the connection of the power supply to the terminals A1 and A2 an internal test is
started. During this test the output contacts are open and the LED OK is illuminated red
(picture 2a).
The unit is ready after a faultless test displayed via the green illuminated LED OK (picture 2b).
Figure 2a
Figure 2b
Device test
Standstill

5 Monitored function

A standstill is detected by evaluating the induced voltage (EMF) on a decelerating motor. The
output contacts open immediately if the EMF voltage exceeds the voltage set on the device.
The STOP LED goes out (Figure 2c).
When the set voltage is not reached, the configurable On delay is active. The STOP LED
flashes green (Figure 2d).
At the end of the delay time, the output contacts close. The STOP LED lights up green
(Figure 2b). The mechanical blockade of the motor is not being monitored.
6 Function of the control inputs I11 und I22
The standstill monitor is inactive when I11 and I22 are connected with 24 V DC. See table 1.
The standstill monitor is only active in FA1. The protective equipment is unlocked during a
standstill.
Table 1: Selecting the mode
I11
I22
Function mode
0 V
0 V
FA1
24 V
0 V
Not allowed!
0 V
24 V
Not allowed!
24 V
24 V
FA2
For applications with synchronous motors, the switching threshold may only be adjusted
within a range of 1 ... 7. If set within a range of 8 ... 15, the motor standstill can be
detected prematurely.
6
7
8
9
75
80
200
230
120
120
1000
1000
Parameters cannot be changed while a fault is present, e.g. wire breakage or disconnected
motor!
6
7
8
9
5
6
7
8
Figure 2c
Figure 2d
Movement
Run-out
Description
Output contacts are only closed during standstill.
Output contacts are closed also during movement.
WARNING
10
11
12
13
250
300
350
400
1000
1000
1000
1000
CAUTION
10
11
12
13
10
12
14
16
14
15
460
500
1000
1000
14
15
18
20
6 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Svm 4001k-c

Table of Contents