4.3 Preparation

PM300-BTJ and PM335J-NODE systems are designed with the concept of 'Plug in and Play' in mind. To complete the easy installation, a
screw driver and DC cables are required. Follow Table 5 recommendation for minimum wiring size.
CURRENT
MINIMUM CABLE SIZE
0–5A
1.0mm
or 18 AWG
2
5–10A
2.0mm
or 14 AWG
2
10–15A
3.0mm
or 13 AWG
2
15–20A
4.0mm
or 11 AWG
2
20–25A
5.0mm
or 10 AWG
2
25–30A
6.0mm
or 9 AWG
2
Table 5 Minimum cable size

4.4 Connection

PM335J transformer unit is designed with a spring and screw terminal. Please refer to following illustration at right.
Each type of terminal is designed to fit a different range of cables.
TYPE
TERMINAL MODEL
NUMBER
Type 1
ERTB10-10.16
Type 2
Wago804-114
Type 3
Wago2704-103
Table 6 Recommended terminal and cable gauge
TYPE 1
Figure 19 Connection of Terminal Type 1
TYPE 2
Figure 20 Connection of Terminal Type 2
14
SUITABLE CABLE
GAUGE
0.5mm
– 10mm
2
2
0.25mm
– 2.5mm
2
2
0.5mm
– 6mm
2
2
When running cables, if they pass through panels or wall, ensure the
cables are protected from damage by sharp edges. In such cases, it is
recommended to use cable glands.
Type 1
Type 2
Figure 18 PM335J Terminals
TYPE 3
Figure 21 Connection of Terminal Type 3
Type 3