Component Identification - M-system R7D-DA16 Instruction Manual

Discrete input module, 16 points

Advertisement

COMPONENT IDENTIFICATION

(A)
(B)
(C)
1 2 3 4 5 6 7 8
X10
X1
MS
NS
NODE ADD.
B.RATE
10 11 12 13
1
2 3 4
5
1
2
(G)
(A) Status Indicator LED
(B) Node Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) Discrete Input Status Indicator LED
(G) DeviceNet, Power Supply Terminals
(H) Input Terminals
■ STATUS INDICATOR LED
ID
STATE
TO INDICATE
MS
Green
Operating in a normal condition
Blinking Green
Standby (needs commissioning)
Red
Critical failure
Blinking Red
Minor failure
OFF
No power supplied
NS
Green
Link on-line and connections in the
established state
Blinking Green
Link on-line but no connections in
the established state
Red
Critical link failure
Blinking Red
Minor link failure
OFF
No power supplied
■ DISCRETE INPUT STATUS INDICATOR LED
LED red indicators show the signal status.
ON : LED ON
OFF : LED OFF
■ NODE ADDRESS
Node Address is selected between 1 and 63 in decimal. The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.
(D)
(E)
(F)
0 1 2 3 4 5 6 7 8 9 A B C D E F
CNFG.
14
15 16 17 18
3
4
5
6
7
8
9
(H)
Factory setting : 00
Node Address Setting (x1)
Node Address Setting (x10)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
■ BAUD RATE
Baud Rate is selected with the rotary switch.
0 : 125 kbps (factory setting)
1 : 250 kbps
2 : 500 kbps
3 thr. 9 : Auto-tracking
The R7D communicates in the baud rate setting detected at
the startup with the switch set to the positions 0 (125 kbps),
1 (250 kbps) or 2 (500 kbps).
For the settings 3 through 9, it analyzes the PLC' s network
to determine the baud rate on the network.
■ OPERATING MODE
• Extension: SW1-1, 1-2
SW1-1
SW1-2
EXTENSION
OFF
OFF
No extension (*)
ON
OFF
Discrete input, 8 or 16 points
OFF
ON
Discrete output, 8 or 16 points
(*) Factory setting
Note: Be sure to set unused SW1-3 through 1-8 to OFF.
■ DeviceNet TERMINAL ASSIGNMENT
1
2
NO.
ID
1
V+
2
CAN_H
3
Drain
4
CAN_L
5
V–
■ INPUT TERMINAL ASSIGNMENT
10
11
12
13
COM2
X1
X3
X5
1
2
3
4
5
COM1
X0
X2
X4
NO.
ID
FUNCTION
1
COM1 Common
2
X0
Input 0
3
X2
Input 2
4
X4
Input 4
5
X6
Input 6
6
X8
Input 8
7
XA
Input 10
8
XC
Input 12
9
XE
Input 14
■ EXTENSION MODULE
Combinations with all extension modules are selectable.
R7D-DA16
Baud Rate Setting
3
4
5
FUNCTION, NOTES
Network power supply +
Network data High
Shield
Network data Low
Network power supply –
14
15
16
17
18
X7
X9
XB
XD
XF
6
7
8
9
X6
X8
XA
XC
XE
NO.
ID
FUNCTION
10 COM2 Common
11
X1
Input 1
12
X3
Input 3
13
X5
Input 5
14
X7
Input 7
15
X9
Input 9
16
XB
Input 11
17
XD
Input 13
18
XF
Input 15
EM-7802-F Rev.5 P. 2 / 10