M-system R7M-EC8B/UL Instruction Manual

Pnp transistor output extension module, 8 points

Advertisement

Quick Links

INSTRUCTION MANUAL
PNP TRANSISTOR OUTPUT EXTENSION MODULE, 8 points

BEFORE USE ....

Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Discrete output extension module ............................... (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
SEN TRONIC
(Modbus)
056 222 38 18
mailbox@sentronic.com
AG
MODEL
POINTS OF CAUTION
■ NONINCENDIVE APPROVAL OPTION
• This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D or Non-Hazardous Locations only.
• WARNING! – Explosion Hazard –
Substitution of any component may impair suitability for
Class I, Division 2.
• WARNING! – Explosion Hazard –
DO NOT disconnect while the circuit is live or unless the
area is known to be free of ignitable concentrations.
• Temperature Code of this equipment is T5 and the Maxi-
mum Ambient Temperature is 55°C (Surrounding Tem-
perature inside the fire enclosure).
■ CONFORMITY WITH UL APPROVAL
• This equipment is suitable for use in Installation Catego-
ry II and in a Pollution Degree 2 environment.
• Altitude up to 2000 meters
• This equipment must be mounted inside a suitable fire
enclosure.
• This equipment is to be supplied by a Class 2 power sup-
ply.
■ CONFORMITY WITH EC DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
www.sentronic.com
R7M-EC8B
R7M-EC8B
EM-7803-P Rev.
P.  / 6

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the R7M-EC8B/UL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for M-system R7M-EC8B/UL

  • Page 1 (Modbus) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ NONINCENDIVE APPROVAL OPTION contents of the package you received as outlined below. • This equipment is suitable for use in Class I, Division 2, If you have any problems or questions with the product, Groups A, B, C, D or Non-Hazardous Locations only.
  • Page 2 R7M-EC8B COMPONENT IDENTIFICATION CONNECTION DIAGRAM Connect the unit as in the diagram below. Discrete I/O Status Indicator LED +24V 0 1 2 3 4 5 6 7 Output Terminals ■ DISCRETE I/O STATUS INDICATOR LED Discrete I/O modules including those for extensions have LED indicators showing I/O signal status.
  • Page 3 CE mark which shows that the product conforms with the requirements of EC Directive. Each EC Directive describes the scope of apparatuses to which that EC Directive is applied. M-System’s R7M must conform with EMC Directive. Each Directive states only basic requirements. In order to mark the CE on an assembled machinery equipment, its manufac- turer needs to check the overall conformity with Directives applicable to it.
  • Page 4 R7M-EC8B • Points of cautions applicable when installing the R7M Series Install the R7M Series inside Keep the opening for a control panel. ventilation as small as posible. Attachment part of earth clamp should be fixed with screw in conduction with the Attach an electro- internal panel plate.
  • Page 5 R7M-EC8B ■ WARNINGS AND CAUTIONS WHEN LAYING CABLES Signal cables connected to the R7M contain high-frequency components. Since these cables has the same effect as an an- tenna, they emit these high-frequency components to the external space as noise or overlaps noise from the external space on themselves.
  • Page 6 To external apparatus Grounding in pig tail form Motor is not effective. Drive Cable Maintain distance between cables and noise sources. M-SYSTEM WARRANTY M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice. THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER. M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: info@m-system.co.jp EM-7803-P Rev....

This manual is also suitable for:

R7m-ec8b

Table of Contents