3. Controls and Adjustments

a) Default Dip Switch Settings

The dip switch is factory-adjusted to the positions listed below. Note that the settings
vary for KM-1601SRH and KM-1601SRH3 depending on the water valve installed. The
code stamped on the 3U0111-01 and 3U0111-02 water valves faces the rear of the unit.
The code stamped on the 4A1176-04 water valve faces the front of the unit.
Auxiliary
Model
Code
KM-1601SWH
Dip switch settings for water-cooled
KM-1601SWH3
units are as listed, regardless of
auxiliary code.
KM-1601SRH
R-0, R-1,
KM-1601SRH3
some S-1
Some S-1
S-2 and later
b) Harvest Timer (dip switch 1 & 2)
The harvest timer starts counting when the thermistor reads 48°F (9°C) at the evaporator
outlet.
No adjustment is required under normal use, as the harvest timer is adjusted to the
suitable position. However, a setting longer than the factory setting may be advised in
cases where the flush provided at harvest needs to be prolonged for extra cleaning.
Before changing this setting, call the HOSHIZAKI Technical Support Department at
1-800-233-1940 for recommendations. Keep in mind that setting the harvest timer to a
longer setting will decrease 24 hour production.
Water
Stamp
Valve Part
on Water
Number
Valve
OFF OFF OFF OFF ON ON OFF OFF OFF ON
3U0111-02
J248-032
(8 l/min)
3U0111-01
J248-030
(15 l/min)
4A1176-04 (11 l/min)
Freeze Timer (9 & 10)
Normally off.
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
Dip Switch Setting
No. 1
No. 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
1
Dip Switch No.
1
2
3
4
5
ON OFF ON OFF OFF OFF OFF OFF OFF OFF
ON OFF OFF OFF ON ON OFF OFF OFF OFF
Time
(seconds)
60
90
120
180
6
7
8
9
10