Omega OME-ET-7000 Series User Manual page 85

Ethernet i/o modules
Table of Contents

Advertisement

Step 3
Configure the Modbus Settings for the OME-PET-7026
Click the "Pair Connection" option in the "Configuration" section of
the Main Menu and enter the details noted in the table below info the
respective fields.
Field
I/O Pair
Connection
Remote IP
Address
Remote TCP Port
Connection
Timeout
Reconnect Interval 5000 ms
Remote Net ID
To determine the Net ID, check the "Modbus Definition" section on the
"Common Function" page, which can be found by clicking the "Module I/O
Settings" option in the "Configuration" section of the Main Menu.
Scan Time
Access Type
Local AO Base Address
Remote AI Base
Address:
I/O Count
Communication Timeout
Settings
Select this option to enable the I/O pair connection
functions.
This is the IP address of the OME-ET-7017 (e.g.
192.168.1.204)
502
3000 ms
1 (Default = 1, the Net ID for the OME-ET-7017)
300 ms
Select AO
0, (Starting from AO0 on the OME-PET-7026)
0, (Starting from AI0 on the OME-ET-7017)
2, (Using AO0, AO1 and AI0, AI1)
400 ms
Page: 80