Type Code
Input Range
Platinum 100
α=0.003916
24
-100 ~ 100°C
Platinum 100
α=0.003916
25
0 ~ 100°C
Platinum 100
α=0.003916
26
0 ~ 200°C
Platinum 100
α=0.003916
27
0 ~ 600°C
Nickel 120
28
-80 ~ 100°C
Nickel 120
29
0 ~ 100°C
Platinum 1000
α=0.00385
2A
-200 ~ 600°C
Cu 100
α=0.00421
2B
-20 ~ 150°C
Cu 100
α=0.00427
2C
0 ~ 200°C
Cu 1000
α=0.00421
2D
-20 ~ 150°C
Data Format
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
Engineering Unit
2's comp HEX
+F.S
+10000
7FFF
+10000
7FFF
+20000
7FFF
+6000
7FFF
+10000
7FFF
+10000
7FFF
+6000
7FFF
+15000
7FFF
+20000
7FFF
+15000
7FFF
-F.S
-10000
8000
0
0000
0
0000
0
0000
-8000
999A
0
0000
-2000
D556
-2000
EEEF
0
0000
-2000
EEEF