Omega OME-ET-7000 Series User Manual page 115

Ethernet i/o modules
Table of Contents

Advertisement

Step 3
Set the type code to the type you want to calibrate.
Select the AI range (e.g. 09, -5V ~ 5V) then click "Submit" button.
Step 4
Enable calibration.
We will use the software – Modbus Master Tool - to complete the step 4 ~ 8.
The complete version of the Modbus Master Tool can be obtained from the
companion CD:
CD:\Software\Modbus_Master_Tool\
Please double-click the "ModbusMasterToolPC.exe" to open it and
4.1
click the "Setup > Definition" in menu bar to setup the parameters.
1.
3.
3.
2.
It depends on the settings in Modules I/O Settings -
Modbus Definition (refer to Section 3.2.3)
Select "01 Read Coils Status" (no
matter what kind of module you use).
Rrefer to the table below - Modbus
Address for Calibration. (830 ~ 832)
2.
Page: 110