Chapter 2: Installation
Panel terminals
Figure 5 below shows an overview of panel terminals. The following sections
provide details on how to connect devices to the panel.
Figure 5: Panel terminals
GND
B
16.5 VAC
+12V
A
SPKR SPKR
1
2
3
4
5
6
7
Zones
The panel comes with factory programmed onboard hardwired zones. Install 2
kohm, end-of-line (EOL) resistors on all unused factory programmed onboard
hardwired zones. If you don't want to install EOL resistors, delete any unused
zones from memory.
Zone inputs 1 through 8 are supervised using the included 2-kohm, end-of-line
resistors at the last device on each circuit. All eight zones accept either normally
open (NO) or normally closed (NC) detection devices.
14
GND ZONE1 ZONE2 GND ZONE3 ZONE4 GND ZONE5 ZONE6 GND ZONE7 ZONE8 GRN
OUT1 OUT2 +12V
MIC
8
9
10
11
12
13
14
SW SW GND #1 #2
15
16
17
18
19
21
20
_
+
NC COM
BRN
GRY
RED
22
23
24
25
26
27
28
GRY
BRN
(-) (+)
GRN
RED
(-) (+)
RING
TIP
(+)
(-)