Chapter 2: Installation
Table 4 below describes the maximum wire length allowed between compatible
devices and the panel, and the minimum and maximum current draw of each
device.
Table 4: Wire length requirements
Device
SuperBus 2000 2x16 LCD alphanumeric
touchpad
SuperBus 2000 ATP 1000 alphanumeric
touchpad
SuperBus 2000 ATP 2100 alphanumeric
touchpad
SuperBus 2000 ATP 2600 alphanumeric
touchpad
SuperBus 2000 fixed display touchpad
SuperBus 2000 FTP 1000 fixed display
touchpad
SuperBus 2000 RF transceiver
SuperBus 2000 phone interface/voice module
SuperBus 2000 voice-only module
SuperBus 2000 2 amp power supply
4 input/2 output SnapCard
8Z hardwired zone expander SnapCard
4 output SnapCard
SuperBus 2000 8Z input module
SuperBus 2000 4-relay output module
8
Max. wire
Standby mA
length to
draw
panel
22 ga.: 300 ft.
15 mA
18 ga.: 750 ft.
22 ga.: 300 ft.
12 mA
18 ga.: 750 ft.
22 ga.: 300 ft.
30 mA
18 ga.: 750 ft.
22 ga.: 300 ft.
30 mA
18 ga.: 750 ft.
22 ga.: 300 ft.
11 mA
18 ga.: 700 ft.
22 ga.: 300 ft.
12 mA
18 ga.: 700 ft.
22 ga.: 1,000
45 mA
ft.
18 ga.: 2,500
ft.
22 ga.: 40 ft.
25 mA
18 ga.: 120 ft.
22 ga.: 40 ft.
20 mA
18 ga.: 120 ft.
No load
N/A
20 mA
N/A
38 mA
N/A
1 mA
22 ga.: 1,800
18 mA
ft.
18 ga.: 4,000
ft.
22 ga.: 350 ft.
12 mA
18 ga.: 900 ft.
Alarm mA draw
90 mA
110 mA
165 mA
165 mA
65 mA
75 mA
55 mA
600 mA
300 mA (jumper)
600 mA (no
jumper)
No load
185 mA*
230 mA*
130 mA*
35 mA
180 mA
Concord 4 Installation Manual