IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
CAUTION – The IPS Test Button Component serves as the unit connector. The ILBDW FBS will initiate once
1.
the IPS installation is complete ("S" models only) and A.C. power is supplied to the unit.
2.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by decom-
missioning the IPS Test Button Component before servicing (see Page 4 - Maintenance).
3.
CAUTION – This equipment provides reduced current levels when higher voltage loads are connected. Load
calibration is required to ensure proper operation (see page 4).
CAUTION – This is a sealed unit. Components are not replaceable. Replace the entire unit when necessary.
4.
5.
CAUTION – Installation and servicing should be performed by qualified personnel only.
The ILBDW is for use with grounded LED luminaires listed to UL standards. Not for use in heated air outlets
6.
or hazardous locations.
The ILBDW FBS and A.C. driver must be on the same branch circuit.
7.
8.
Do not mount near gas or electric heaters.
9.
The ILBDW FBS should be mounted in locations and at heights where it will not readily be subjected to tam-
pering by unauthorized personnel.
10.
Product output voltage varies according to wattage. Refer to Illustration 1 for output voltage per model.
11.
The ILBDW FBS is certified in the CA Title 20 Modernized Appliance Efficiency Database System (MAEDBS)
as a small battery charger.
12.
Suitable for use in wet locations.
13.
For use in 0° C minimum, 48° C maximum ambient temperatures.
14.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition,
prevent proper performance, void warranty, and result in non-compliance with UL specifications.
15.
Do not use this equipment for other than intended use.
16.
Install in accordance with the National Electrical Code and local regulations.
17.
Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation. See addendum for compatibility and covered luminaire requirements.
EMERGENCY LED DRIVER FOR USE
WITH LED LUMINAIRES IDENTIFIED
IN THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS
E484840
ILBDW FBS
"S" OR "SLTEST" MOUNTING STYLE
FOOD AND BEVERAGE SAFE
WET LOCATION EMERGENCY
LIGHTING EQUIPMENT FOR LED
INSTRUCTION MANUAL
SAVE THESE INSTRUCTIONS
COMPONENT
HIGH EFFICIENCY PERFORMANCE
MEETS CA T20 BATTERY CHARGER
EFFICIENCY STANDARDS
For Models:
ILBDW CP[#] HE SD S FBS
ILBDW CP[#] HE SD HV S FBS
ILBDW CP[#] HE SD SLTEST FBS
ILBDW CP[#] HE SD HV SLTEST FBS

Advertisement

loading

Summary of Contents for IOTA ILBDW FBS

  • Page 1 The ILBDW FBS and A.C. driver must be on the same branch circuit. Do not mount near gas or electric heaters. The ILBDW FBS should be mounted in locations and at heights where it will not readily be subjected to tam- pering by unauthorized personnel.
  • Page 2: Installation Instructions

    PVC conduit. PVC CONDUIT ILBDW (”SLTEST” models) IOTA provides several mounting accessories to enable suspended or surface mounting of the ILBDW that can be acquired by contacting Customer Service or your local Sales Representative. GASKET (PROVIDED) ILBDW S AND SLTEST - CONNECTIONS TO NORMAL DRIVER AND LED LOAD...
  • Page 3: Completing Installation

    ILBDW S AND SLTEST - AC INPUT CONNECTIONS COMPLETING INSTALLATION STEP 4 - WIRING THE AC INPUT The ILBDW requires an unswitched AC input of 120-277 volts. Connect the BLACK wire to the 120-277 Line, the WHITE wire to the Neutral, and the GREEN wire to Ground. CONDUIT BLACK (120-277V, 50/60HZ) ILBDW...
  • Page 4: Testing And Maintenance

    TESTING & MAINTENANCE Automatic Testing Table A: IPS Diagnostic Codes The ILBDW is designed to automatically test the emergency STATUS INDICATION CONDITION function for 60 seconds each month, and BATTERY IS CHARGING 90 minutes every 12 months. GREEN BATTERY IS FULLY CHARGED Self-testing works in conjunction with the IPS assembly.
  • Page 5 The purpose of this addendum is to sufficiently identify electrical compatibility and predictable emergency light output of the LED luminaire when used with the IOTA ILBDW CP Series LED emergency drivers. Verification of these operat- ing traits does not constitute a code-compliant, as-installed emergency egress system. It is still the responsibility of the Designer/Specifier to assure appropriate light levels are achieved during emergency operation of the luminaire in accor- dance with Federal, state and local municipal codes regarding path of egress illumination.

This manual is also suitable for:

Ilbdw cp he sd s fbsIlbdw cp he sd hv s fbsIlbdw cp he sd sltest fbsIlbdw cp he sd hv sltest fbs