Knk03; Knk03 Ratings - Bosch rexroth IndraDrive Mi KMV03 Instruction Manual

Distributed supply unit/distributed mains filter
Hide thumbs Also See for rexroth IndraDrive Mi KMV03:
Table of Contents

Advertisement

10/29
Ratings and dimensions
2.2

KNK03

2.2.1

KNK03 ratings

Description
Listing according to UL standard
Listing according to CSA standard
UL‑Files
Pollution degree
Ambient temperature range with
nominal data
Ambient temperature range with
reduced nominal data
Mass
Device height
1)
Device depth
2)
Device width
3)
Minimum distance on the top of
the device
Minimum distance on the bottom
of the device
Horizontal spacing at the device
Short circuit current rating
Rated input voltage, power
4)
Tolerance rated input voltage U
Mains frequency
Tolerance input frequency
Rated input current
Branch circuit protection fuse
Required wire size in accordance
with NFPA 79 and UL 508 A (in‐
ternal wiring);
6)
Field wiring material (material;
conductor temperature; class)
Output current
Power dissipation at continuous
current and continuous DC bus
power respectively
Bosch Rexroth AG R911374765_Edition 01
UL ratings and dimensions
Symbol
Unit
T
°C
amax
T
°C
amax_red
m
kg
H
mm
T
mm
B
mm
d
mm
top
d
mm
bot
d
mm
hor
SCCR
A rms
U
V
LN_nenn
%
LN
f
Hz
LN
Hz
I
A
LN
A
5)
A
AWG
LN
I
A
out
P
W
Diss_cont
1) 2) 3)
Housing dimension; see also related dimensional drawing
IndraDrive Mi KMV03 Distributed Supply Unit KNK03 Distrib‐
KNK03.1A-
KNK03.1A-
NR-A0008-P-
NR-B0012-P-
U226-A4
U226-A4
UL 61800-5-1
CSA C22.2 No. 274-13
E134201
24.00
360
280
270
42000
3x AC 380...500
50...60
8.1
12.0
15
15
min 14
Cu; 60/75° C; 1
8.1
12.0
147
175
uted Mains Filter
KNK03.1A-
KNK03.1A-
NR-I0002-P-
NR-W0010-P-
U226-A4
U226-A4
2
40
55
20.00
24.00
280
360
220
280
270
270
0
0
0
±10
±2
2.3
9.5
6
15
2.3
9.5
104
160

Hide quick links: