Download Print this page

M-system R3-NC3 Instruction Manual page 5

Cc-link interface module

Advertisement

•Module Status
RX(n+0)0 through RX(n+0)F indicate whether individual I/O module are mounted or not. The bit corresponding to the mounted
slots turns to "1," and the unmounted slots to "0."
•Error Status
RX(n+1)0 through Rx(n+1)F indicate error status for each module as described below. The bit corresponding to such modules
turns to "1."
R3-TSx, R3-RSx, R3-US4: Input burnout
R3-DA16A:
R3-YSx:
•Data Error Status
RX(n+2)0 through Rx(n+2)F indicate overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status
for each module. The bit corresponding to such modules turns to "1."
•RX(n+3) through RX(n+m*7–2) are unused.
•RX(n+m*7–1)0 through RX(n+m*7–1)7 are reserved for future use. RX(n+m*7–1)B is assigned to Ready signal, which is
turned to "1" when the network module is in normal conditions. RX(n+m*7–1)8 through RX(n+m*7–1)A, RX(n+m*7–1)C
through RX(n+m*7–1)F are not used.
RX(n+0) 0, RX(n+1) 0, RX(n+2) 0
RX(n+0) 1, RX(n+1) 1, RX(n+2) 1
RX(n+0) 2, RX(n+1) 2, RX(n+2) 2
:
RX(n+0) F, RX(n+1) F, RX(n+2) F
15
F E D C B A 9 8 7 6 5 4 3 2 1
RX(n+0)
RX(n+1)
RX(n+2)
RX(n+m*7–1)
Power input in error or disconnected
Output current error (e.g. load unconnected)
Module 1
Module 2
Module 3
:
Module 16
0
0
Module Status
Error Status (Burnout Bit)
Data Error Status
Unused
Reserved Bit
P. 5 / 7