Misfire of burner

10.5 In Case of Power Failure

If power failure occurs while the chiller-heater is operating in cooling mode and the chiller-heater is
left as it is without taking no countermeasures, crystallization may take place because of no dilution
operation. In case of power failure, open the damp valve located at the lower part of the low
pressure generator to drain the concentrated solution. Further, if power failure happens while
purging, close the manual purge valve (Refer to Fig. 6.2 Purge System) quickly. For restoration,
start the chiller-heater in the same procedure as taken in case of crystallization.
10.6 In Case of Emergency Like Earthquake or Fire
Switch off the main power and close the main fuel valve quickly.
The fuel shut-off valve is closed automatically by the force of spring if the power is cut. Open the
main fuel valve to restart the chiller-heater after confirming safety.
( Poor igniter transformer
( Dirty and poor flame detector
( Failed actuation of the fuel shut-
off valve
( Failed protect relay
( Improper air-fuel ratio
59
( Check and replace with new
igniter transformer
( Check and replace with new
flame detector
( Check and replace with new gas
shut-off valve
( Check and replace with new
protect relay
( Check and adjust air-fuel ratio