Heating Cycle - Hyundai HDFN-80-1400 Operation Instructions Manual

Gas/ oil direct-fired absorption chiller-heater
Table of Contents

Advertisement

Point g~h
Point h~I
Point i~a
2.2
Heating Cycle (See Fig.2.1 B)
The refrigerant vapor going out from the high pressure generator is sent to the evaporator and
heats the hot water up to the required high temperature. The circulation of the solution applies
correspondingly to the cooling cycle mentioned above.
generator and is mixed with the concentrated solution from the low pressure
generator.
: A state where the concentrated solution going out from the low pressure
generator is cooled down in the low temperature heat exchanger.
: A state where the concentrated solution is sprayed on the surface of the
absorber tubes to be cooled down in the low temperature heat exchanger.
: A state where the concentrated solution absorbs the refrigerant to be diluted in
the absorber.
15

Advertisement

Table of Contents
loading