Joint Trim; Plumbing; Waste Outlet And P-Trap; Installing Condensate Drain - Remote - Hussmann RBB Installation And Operation Manual

Upright back bar deli case
Hide thumbs Also See for RBB:
Table of Contents

Advertisement

DO NOT USE PERMAGUM!
It is the contractor's responsibility to install
case(s) according to local construction and
health codes.
5. Slide second case up to first case snugly. Then level
second case to the first case so glass front, bumper
and top are flush.
6. Attach sections together via a bolt located in top of
case (see diagram and lock camlock in place).

Waste Outlet and p-trap

The waste outlet is located off the center of the case, 8"
from the front.
A 3/4" P-TRAP and threaded adapter are supplied with
each fixture. The P-TRAP must be installed to prevent air
leakage and insect entrance into the fixture.
NOte:
pvc-dWv solvent cement is recommended.
Follow the hussmann's instructions.

installing condensate drain - remote

Poorly or improperly installed condensate drains can
seriously interfere with the operation of this refrigerator, and
result in costly maintenance and product losses. Please
follow the recommendations listed below when installing
condensate drains to insure a proper installation:
1. Never use pipe for condensate drains smaller
than the nominal diameter of the pipe or P-TRAP
supplied with the case.
. When connecting condensate drains, the P-TRAP
must be used as part of the condensate drain
to prevent air leakage or insect entrance. Store
plumbing system floor drains should be at least 14"
off the center of the case to allow use of the P-TRAP
pipe section. Never use two water seals in series in
any one line. Double P-TRAPS in series will cause a
lock and prevent draining.
installation (cont'd)

Joint trim

After cases have been leveled and joined and refrigeration,
electrical and wasted piping work completed, install the
splashguards. Fasten along the top edge, or center, with
#10 X 3/3" sheet metal screws.
DO NOT SEAL JOINT TRIM TO FLOOR!

plumbing

3. Always provide as much down hill slope ("fall") as
possible; 1/8" per foot is the preferred minimum.
PVC pipe, when used, must be supported to
maintain the 1/8" pitch and to prevent warping.
4. Avoid long runs of condensate drains. Long runs
make it impossible to provide the "fall" necessary for
good drainage.
5. Provide a suitable air break between the flood rim of
the floor drain and outlet of condensate drain. 1" is
ideal.
6. Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should
be insulated with a nonabsorbent insulation
material such as Armstrong's Armaflex.
b. Where condensate drains are located in dead
air spaces (between refrigerators or between a
refrigerator and a wall), provide means to prevent
freezing. The water seal should be insulated to
prevent condensation.
4
igup-rbb-0608
Bolt
Camlock
Silicone