HUSSMANN CHINO PRODUCT CONTROL The serial number and shipping date of all equipment has been recorded in Hussmann’s files for warranty and re- placement part purposes. All correspondence pertaining to warranty or parts ordering must include the serial num- ber of each piece of equipment involved, in order to pro- vide the customer with the correct parts.
RDI-27 2-Well 3-Well Scale = 1/4" Scale = 1/4" Three sample modules are shown above. The RDI has been engineered for lengths from 1-Well up to 11-Wells in one full pan or one pan & rd design. " Flange (30 "...
2. All plumbing should conform to local codes. 3. When the RDI is to be installed in an existing fixture or in a supplied fixture, the RDI and the new or existing fixture should be leveled front to back and side to side.
Rev.0209 DRAINAGE. NOTE: A. To avoid removing concrete flooring, begin lineup leveling from the highest point of the store floor. B. When wedges are involved in a lineup, set them first. All cases were leveled and joined prior to shipment to insure the closest possible fit when cases are joined in the field.
4. Subtract the saturation temperature obtained in step No. 2 from the temperature measured in step No. 3. 3. The difference is superheat. 5. Set the superheat for 5°F - 7°F. T-STAT LOCATION T-Stats are located within the electrical raceway. Refer to diagram below. IGSS-RDI-0209...
Hussmann cases were not designed to “heat up” or “cool down” product—but rather to maintain an item’s proper temperature for maximum shelf life. To achieve the pro- tection required always: 1.
TOWARD THE MOTOR. COPPER COILS The copper coils used in Hussmann merchandisers may be repaired in the field. Materials are available from local refrigeration wholesalers. Hussmann recommends using #15 Sil-Fos for repairs.
10 Well 20° 38° 30° 125 per Well 11 Well 20° 38° 30° 125 per Well RDI Standard Back to Back 20" - 27" Deep Pans 2 Well 20° 38° 30° 125 per Well 4 Well 20° 38° 30° 125...
Does the system use the recommended compressor? APPENDIX D. – Recommendations to user 1.0 Hussmann Corporation provides instructions and recommendations for proper periodic cleaning. The user will be responsible for such cleaning, including the cleaning of low temperature equipment within the compartment and the cooling coil area(s).
Page 17
On Hussmann refrigeration systems, an additional (4) year extended warranty for the motor/compressor assembly is available, but must be purchased prior to shipment to be in effect. Hussmann reserves the right to inspect the job site, installation and reason for failure.
The MODEL NAME and SERIAL NUMBER is required in order to provide you with the correct parts and information for your particular unit. They can be found on a small metal plate on the unit. Please note them below for future reference. MODEL: SERIAL NUMBER: IGSS-RDI-0209...