Refrigeration; Piping; Refrigeration Lines; Control Settings - Hussmann CR3-F Installation And Operation Manual

Combination service and self-service meat/fish case with rear storage
Hide thumbs Also See for CR3-F:
Table of Contents

Advertisement

Piping

The refrigerant line outlets are located under the case.
Locate first the electrical box, the outlets are then on the
same side of the case but at the opposite end. Insulate
suction lines to prevent condensation drippage.

refrigeration lines

Liquid
3/8" O.D.
note:
the standard coil is piped at
the store tie-in may vary depending on the number of
coils and the draw the case has. depending on the case
setup, the connecting point in the store may be
or 1
/
". refer to the particular case you are hooking up.
1
8
Refrigerant lines should be sized as shown on the
refrigeration legend furnished by the store.
Install P-traPS (oil traps) at the base of all suction line
vertical risers.
Pressure drop can rob the system of capacity. To keep the
pressure drop to a minimum, keep refrigerant line run as
short as possible, using the minimum number of elbows.
Where elbows are required, use long radius elbows only.

Control Settings

See R3(CR3)-M/F technical data sheet for the appropriate
settings for your merchandiser. Maintain these parameters
to achieve near constant product temperatures. Product
temperature should be measured first thing in the morning,
after having been refrigerated overnight. Defrost times
should be as follows: OFF CYCLE - Defrost times should
be as directed in the R3(CR3)-M/F technical data sheet.
The number of defrosts per day and the duration of the
defrost cycle may be adjusted to meet conditions present
at your location.
access to thermostatic expansion valve (teX) and
drain lines
mechanical - Remove product from end of case. Remove
product racks. Remove refrigeration and drain access
panels (labeled). TEX valve (mechanical only) and drain
are located under each access panel at end of the case.
electronic - The Electronic Expansion valve master and
slave cylinder(s) are located within the electrical access
panel(s).

electronic expansion valve eev (optional)

A wide variety of electronic expansion valves and case
controllers can be utilized. Please refer to EEV and
controller manufacturers information sheet. Sensors for
electronic expansion valves will be installed on the coil inlet,
coil outlet, and in the discharge air. (Some supermarkets
require a 4th sensor in the return air). Case controllers will
be located in the electrical raceway or under the case.

thermostatic expansion valve location

This device is located on the same side as the refrigeration
stub. A balanced port expansion valve model is furnished
as standard equipment, unless otherwise specified by
customer.

refrigeration

Suction
5/8" O.D.
/
" (suction); however,
5
8
/
",
/
",
5
7
8
8

expansion valve adjustment

Expansion valves must be adjusted to fully feed the
evaporator. Before attempting any adjustments, make
sure the evaporator is either clear or very lightly covered
with frost, and that the fixture is within 10°F of its expected
operating temperature.

measuring the operating Superheat

1. Determine the suction pressure with an accurate
pressure gauge at the evaporator outlet.
. From a refrigerant pressure temperature chart,
determine the saturation temperature at the
observed suction pressure.
3. Measure the temperature of the suction gas at the
thermostatic remote bulb location.
4. Subtract the saturation temperature obtained in step
No.  from the temperature measured in step No. 3.
The difference is superheat.
5. Set the superheat for 5°F - 7°F.

evaporator Pressure regulator

An Evaporator Pressure Regulator is installed in the front
of the self service section to maintain a constant discharge
temperature. It is located at the front right side of the case,
under the fan plenum near the TEX Valve.

Service Case temperature Control

Temperature control in the upper section of the CR3 with
the Service Option is done by means of a thermostat and
suction solenoid valve. This controls both temperature
and humidity.

thermostat (t-Stat) location

Thermostats are located within the electrical raceway. Refer
to diagram below. There are also labels on the back of the
case indicating T-STAT location(s).
18
r3(Cr3)-m/f-0608
T-Stat &
Ballast Are
Labeled as
Such
Figure #3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cr3-mR3R3-mR3-f

Table of Contents