2. Specifications

2.1 BIF-CC

The general specifications of BIF-CC are shown in table 2.1.
Table 2.1 General
specification of BIF-CC
Item
Type name
Power supply
Power consumption
External dimensions
Operating ambient temperature
Storage ambient temperature
Operating/Storage
ambient humidity
Operating/Storage ambience
Operating altitude
Installation
The functional specifications of BIF-CC are shown in table 2.2.
Table 2.2
specifications of BIF-CC
Item
Number of occupied station
Station type
CC-Link version
Communication method
Communication speed
Transmission path format
Maximum transmission distance
Number of units connected
Available remote station number
3)
Connection cable
■1): The above data indicates the case that the Ver. 1.10 compatible CC-Link dedicated cable (110 ohm type) is used.
Maximum transmission distance depends on communication speed and/or kinds of CC-Link cable.
As for details, please refer to
■2): If the system is configured by only BIF-CC, up to 42 units can be connected.
■3): CC-Link dedicated high-performance cables cannot be used with other cables such as CC-Link dedicated cables
or Ver. 1.10 compatible CC-Link dedicated cables. As for details, refer to
CC-Link Partner Association (CLPA)
BIF-CC
100-240V AC・DC (50/60Hz)
3VA (not including BIF-CON)
5VA (including BIF-CON)
100(H) x 90(W) x 65(D)
-5 to +40℃ (However, the average of temperature per 24hours must not exceed +35℃)
-20 to +60℃ (However, the average of temperature per 24hours must not exceed +35℃)
max. 85%RH (no condensation) at the max. +40℃ in the clean air conditions.
Do not use and store in atmospheres with sulfide gas, ammonia gas, etc.
(H
S≤ 0.01ppm, SO
≤ 0.1ppm, NH
2
2
max. 2000m (6600ft.)
35mm IEC rail/Bracket
1 station
Remote device station
CC-Link Ver. 1.10
Broadcast polling method
10Mbps/5Mbps/2.5Mbps/625kbps/156kbps (*selectable)
Bus format (EIA RS-485 conformance)
100m (at 10Mbps)
160m (at 5Mbps)
1)
400m (at 2.5Mbps)
900m (at 625kbps)
1200m (at 156kbps)
Number of units that satisfies following 2 conditions.
●Condition 1: {(1×a)+(2×b)+(3×c)+(4×d)}≤ 64
a: Number of units that occupies 1 station (*BIF-CC corresponds to this type)
b: Number of units that occupies 2 stations
c: Number of units that occupies 3 stations
2)
d: Number of units that occupies 4 stations
●Condition 2: {(16×A)+(54×B)+(88×C)}≤ 2304
A: Number of remote I/O station units
B: Number of remote device station units (*BIF-CC corresponds to this type)
C: Number of local station, standby master station
and intelligent device station units
1 to 64 (*selectable)
CC-Link dedicated cable/CC-Link dedicated high-performance cable/
Ver. 1.10 compatible CC-Link dedicated cable
"CC-Link Cable Wiring Manual" published by CC-Link Partner Association (CLPA)
.
Specifications
≤ 0.25ppm)
3
Specifications
"CC-Link Cable Wiring Manual" published by
E-6
.

Advertisement

Table of Contents
loading