Argo FCW01 User And Installation Manual

Argo FCW01 User And Installation Manual

Fan coil unit wall mounted type

Advertisement

FAN COIL UNIT WALL MOUNTED TYPE
USER AND INSTALLATION MANUAL
INDOOR UNITS
FCW01
FCW02
FCW03
FCW04
Read this manual carefully before installing and using the commercial air
conditioners and keep it for future reference.
If this manual is lost, consult the electronic version on the argoclima.com website.
Argoclima reserves the right to make any changes to this document due to possible
product improvements without prior notice.
V 11/20
22

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FCW01 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Argo FCW01

  • Page 1 FAN COIL UNIT WALL MOUNTED TYPE USER AND INSTALLATION MANUAL INDOOR UNITS FCW01 FCW02 FCW03 FCW04 Read this manual carefully before installing and using the commercial air conditioners and keep it for future reference. If this manual is lost, consult the electronic version on the argoclima.com website.
  • Page 2 To Users Thank you for selecting Argoclima product. Please read this instruction manual carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our product and achieve expected operating effect, we hereby instruct as below: (1) This equipment should be installed, operated or maintained by the qualified servicemen who have had specific training.
  • Page 3: Table Of Contents

    Contents Safety Notices (Please be sure to abide ) ............25 1. Product Introduction ....................29 1.1 Working Principle......................29 1.2 Main Parts ........................29 1.3 Working Conditions ......................30 2. Installation Instructions ..................31 2.1 Installation Dimension Diagram ..................31 2.2 Installation of the Rear Panel ..................32 2.3 Piping Holes for Installation .....................32 2.4 Installation of the Drain Pipe ...................32 2.5 Installation of the Connection Pipe ..................33...
  • Page 4: Safety Notices (Please Be Sure To Abide )

    Fan Coil Unit Wall Mounted Type Safety Notices (Please be sure to abide ) WARNING: If not abide strictly, it may cause severe damage to the unit or the people. NOTE: If not abide strictly, it may cause slight or medium damage to the unit or the people. This sign indicates that the operation must be prohibited.
  • Page 5 Fan Coil Unit Wall Mounted Type WARNING Do not spray or rinse this unit Do not let this unit exposed with water, as it would lead to t o m o i s t , w e t o r c o r r o s i v e malfunction or electrocution.
  • Page 6 Fan Coil Unit Wall Mounted Type NOTE During operation, do not insert Please cut off the power supply fingers or other objects into when this unit is not used for the moving parts, which would long time in consideration of lead to unnecessary injuries.
  • Page 7 Fan Coil Unit Wall Mounted Type This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial or household use by lay persons. Installing the unit in the following places may cause malfunction. If it is unavoidable,please consult the local dealer: (1) The place with strong heat sources,vapors, flammable or explosive gas,or volatile objects spread in the air.
  • Page 8: Product Introduction

    Fan Coil Unit Wall Mounted Type 1. Product Introduction 1.1 Working Principle The cold (hot) water entering the heat exchanger will do heat exchanging with air passing through the surface of the heat exchanger to condition the air temperature and humidity. There is no (cold) hot source for this product itself.
  • Page 9: Working Conditions

    Fan Coil Unit Wall Mounted Type 1.3 Working Conditions (1) The entering water temperature for cooling is suggested to be no less than 5℃ ,otherwise it woule lead to condensate; the entering water temperature for heating is suggested to be not higher than 60 ℃ , otherwise it would lead to corrosion of copper tubes or abnormal noise.
  • Page 10: Installation Instructions

    Fan Coil Unit Wall Mounted Type 2. Installation Instructions 2.1 Installation Dimension Diagram structures. 50cm Fig.2 2.2 Installation of the Rear Panel (1) Always mount the rear panel horizontally. Due to the water tray of the unit has been adopted the both- way drainage design, the outlet of water tray should be adjusted slightly down when installing, that is to take the outlet of the water tray as the center of a circle, the included angle between the evaporator and level should be 0 or more, that is good for condensing water drainage.
  • Page 11: Installation Of The Rear Panel

    Fan Coil Unit Wall Mounted Type Fig.3 (2) Fix the rear panel on the wall with screws. (Where is pre-covered with plastic granula) (3) Be sure that the rear panel has been fixed firmly enough to withstand the weight of an adult of 60kg, further more, the weight should be evenly shared by each screw.
  • Page 12: Installation Of The Connection Pipe

    Fan Coil Unit Wall Mounted Type Inlet water side pipe Outlet water side Tailing2 Tailing1 Inlet side piping Outlet side piping insulation Finally wrapit with tape Water drainage pipe Fig.6 Left Left rear Fig.7 Fixing hook Mounting baord Mounting plate Fig.8 2.5 Installation of the Connection Pipe (1) Align the center of the piping pipe with the relevant valve.
  • Page 13: Installation Of The Water Damper

    Fan Coil Unit Wall Mounted Type FCU pipe Spring washer Be sure there is an Washer interval of 6-7mm when the fitting is completed. O-ring Before installed the two pipes must be tightened with the steps of the connection nut. Connection nut Be sure there is an interval of 6-7mm when...
  • Page 14: Commissioning And Maintenance

    Fan Coil Unit Wall Mounted Type (4) The power must have reliable earthing terminal. Please do not connect the earthingwire with the following: ① Water pipe ② Gas pipe ③ Contamination pipe ④ Other place that professional personnel consider is unreliable (5) The model and rated values of fuses should accord with the silk print on fuse cover or related PCB.
  • Page 15: Air Discharge

    Fan Coil Unit Wall Mounted Type (3) Using the controller, the FCU can select the COOL, HEAT, FAN, DRY to check whether the operation is normal or not. (4) Leave test mode to pressing "ON/OFF" button on the controller. (5) During 5 minute, the FCU would leave test mode automatically without pressing any button. (6) Switch off the FCU, pressing "ON/OFF"...
  • Page 16 Fan Coil Unit Wall Mounted Type Open the front panel, the manual switch is on the edge as Fig.11. Manual switch Fig.11 3.4.2 Care and Cleaning NOTE Turn power off and pull out the power plug before cleaning air conditioner, or it may cause electric •...
  • Page 17 Fan Coil Unit Wall Mounted Type y Reinstall the air filter Reinsert the filters along the direction of arrowhead, and then to cover the cover and clasp it. Fig.13 Fig.14 3.4.3 Installation and Maintenance of Healthy Filter (optional) Installation Instructions ◆...
  • Page 18: Troubleshooting

    Fan Coil Unit Wall Mounted Type Fig.15 Fig.16 Fig.17 Fig.18 4. Troubleshooting 4.1 Error List CAUTION The FCU is not expected to be serviced by users. Incorrect repair may cause electric shock or fire, so please contact an authorized service center for professional service. The following checks prior to contact may save your time and money.
  • Page 19 Fan Coil Unit Wall Mounted Type Phenomenon Troubleshooting Cracking noise: • This is the sound of friction caused by expansion and/ or contraction of panel or other parts due to the change of temperature. The unit can not be started up: •...
  • Page 20: Error Codes

    4.2 Error Codes Error Codes Error Description Indoor unit main board environment temperature sensor error Cooler pipe temperature sensor error Control panel ambient temperature sensor error PG motor stalling protection Jumper error Communication error www.argo clima.com...