2.2.2 Environment Requirement

Item
When a user installs a machine frame array in one machine hall, the
Machine
distance between 2 rows of machine frames should be 3.93 – 4.92 Ft.
Hall Space
(1.2 - 1.5m) and the distance against the wall should be no less than
2.62 Ft. (0.8m).
Electric Isolation, Dust Free
Volume resistivity of ground anti-static material: 1 x 10
Machine
Grounding current limiting resistance: 3.28 Ft.(1M) (Floor bearing should be
Hall Floor
greater than 1186.51 lb/yd
Environment
41- 104°F (5 - 40°C) (sustainable), 32- 113°F (0 - 45°C) (short time)
Temperature
installing air-conditioning is recommended
Relative
20% - 80% sustainable 10% - 90% short time
Humidity
Pressure
12.47 – 15.22 PSI (86 - 105KPa)
Door &
Installing rubber strip for sealing door-gaps and
Window
dual level glasses for window
Wall
It can be covered with wallpaper, or brightness less paint.
Fire
Fire alarm system and extinguisher
Protection
Required device power, air-conditioning power and lighting power are
Power
independent of each other. Device power requires AC power 220V ±10%
50/60Hz or 110V ±10% 50/60Hz. Please carefully check before running.

2.2.3 Grounding Requirement

All function modules' good grounding is the basis of reliability and stability of devices. Also, they
are the most important guarantee of lightning arresting and interference rejection. Therefore, the
system must follow this rule.
Coaxial cables' outer conductor and isolation layer should keep proper electric conducting with
the metal housing of the device.
Grounding conductors must adopt copper conductors in order to reduce high frequency
impedance, and the grounding wire must be as thick and short as possible.
Requirements