Cleaning Of Strainer - Laird LA 5000 Operation Manual

Liquid-air cooling unit
Table of Contents

Advertisement

9.4 Cleaning of Strainer

2
Fig. 11:
Locations of ball valve and strainer
1 Strainer cover
1)
Disconnect the unit from mains.
2)
Remove the side panel.
3)
Close the ball valve.
CAUTION
A small amount of coolant will leak from the pump.
Use a cloth or an appropriate vessel for absorption.
4)
Remove the strainer cover using a metric AF24 wrench.
5)
Take off the strainer and clean it. In case of damage the strainer must be replaced.
6)
Remount the strainer and screw on the cover.
7)
Re-open the ball valve.
8)
Should any coolant leak from the strainer the cover must be screwed on using a little more force.
9)
Remount the side panel.
CAUTION
Risk of damage to the pump, if the unit is operated with a fully closed ball valve!
Never start the unit, when the ball valve is closed.
Laird Thermal Systems s.r.o
29
Operation Manual, 387009851
2 Ball valve
Date: 08/09/2022
Version: 1.0
Maintenance and Cleaning