Specifications - Laird LA 5000 Operation Manual

Liquid-air cooling unit
Table of Contents

Advertisement

Product Description

Specifications

4.4 Specifications
Dimensions and weight
Length:
Width:
Height:
Weight:
Coolant capacity:
Coolant:
Table 4:
Dimensions and weight
Performance data
Cooling capacity:
Throughput:
Noise level @ 1m:
Table 5:
Performance data
Environmental conditions
Operating temperature:
Operating temperature:
Operating relative humidity:
Storage temperature:
Storage relative humidity:
Table 6:
Environmental conditions
Settings
Flow control device
Thermal switch
Maximum pressure
Table 7:
Settings
Electrical characteristics
Mains voltage:
Current draw:
Customer main fuse:
Safety circuit, max input
Table 8:
Electrical characteristics
Laird Thermal Systems s.r.o
16
Operation Manual, 387009851
421 mm
537 mm (w/o hose nipples)
480 mm
40 kg (empty)
6.2 liter
Water or water (70%) / glycol (30%)
5.0 kW (100% Water)
> 6.0 lpm at 6.0 bar
57dB(A) (50Hz)
+5°C ... +50°C (Water)
-10°C ... +50°C (Water 70%/Glycol 30%)
20% ... 80%
-25°C ... +70°C (Empty)
10% ... 95%
4.0 ± 0.1 lpm (opening threshold)
55°C  5°C tolerance, 15°C hysteresis
10.0 ± 0.5 bar
230±10% VAC, 1Ph, 50/60 Hz
3.3 A
5 A T
230VAC, 0,5A, 15W
100VDC, 0,5A, 10W