6 Initial Operation

6.1 Safety Indications Related to Initial Operation

CAUTION
Danger of malfunction caused by faulty connections during initial operation!
Before switching on the unit make sure that
• all safety equipment of the unit is implemented and functional
• all connections were properly made
Please follow the rules in chapter Safety Regulations on page 9.

6.2 Setting to Work

6.2.1 Placement

0.5 m min.
min.minmminmini
Fig. 7:
Minimum clearance for air entrance and air exit
1 Ventilation grid
1)
Move the unit to its installation location as mentioned in chapter 5.2.
2)
Place the unit in a way that air entrance and air exit are not obstructed. Wall clearance must not be less
than 0.5 m, otherwise cooling capacity may be restricted. Unit should not be installed in a corner as hot
air can be recirculated into the cooler.
PLEASE NOTE
In case of storage of the unit at temperatures lower than 5°C or higher than 40°C for longer periods please
wait 3 hours prior to initial operation to allow for temperature adjustment.
Laird Thermal Systems s.r.o
19
Operation Manual, 387009851
1
Safety Indications Related to Initial Operation
0.5 m min.
min.minmminmini
Date: 08/09/2022
Version: 1.0
Initial Operation
1
Liquid-Air Cooling Unit LA 5000
387009381