Connecting Functional Ground - Siemens SIMATIC EMS400S Operating Instructions Manual

Carrier controller
Hide thumbs Also See for SIMATIC EMS400S:
Table of Contents

Advertisement

4.6.2

Connecting functional ground

Make allowances for equipotential requirements when connecting a programming device or
Industry PC.
Potential differences
Potential differences may develop between distributed plant parts. Potential differences can
cause high equalizing currents on the data cables and thus interfere with data transmission
or damage electronic components. Equalizing currents can develop if the cable shielding is
terminated at both ends and grounded to different parts of the system.
Differences in potential can develop when a system is connected to different mains.
General requirements of equipotential bonding
You must reduce potential differences to the possible minimum by installing equipotential
conductors to ensure proper functioning of the respective electronic components. For this
reason, observe the following rules when installing the equipotential bonding circuit:
● The effectiveness of equipotential bonding increases proportionally with lower impedance
● If two plant components are interconnected by means of shielded data cables and their
● The cross-section of an equipotential bonding conductor must be of sufficient size to cope
● Use equipotential bonding conductors made of copper or galvanized steel.
● Use a suitable cable clamp to bond the shielding of the data cable flush to the
● Route the equipotential bonding conductors and data cables in parallel and with minimum
Carrier controller
Operating Instructions, 09/2013, A5E03474162-02
or greater cross-section of the equipotential bonding conductor.
shielding is grounded at both ends, the impedance of the additionally installed
equipotential bonding conductor may not exceed 10 % of the shielding impedance.
with the maximum equipotential current.
In practical life, equipotential bonding conductors with a minimum cross-section of
16 mm² are generally accepted for the interconnection between control cabinets or with
grounding busbars.
Interconnect the equipotential bonding conductors and the earth rod/protective conductor
on a large surface and protect these against corrosion.
equipotential busbar. Keep the length of cable between the HMI device and the
equipotential busbar as short as possible.
clearance between them.