48v, 2.5 a, 120 w, single-phase input
Hide thumbs Also See for Allen-Bradley 1606-XLE120F:

Advertisement

Quick Links

Power Supply - 48V, 2.5 A,
120 W, Single-phase Input
Catalog Number 1606-XLE120F
Reference Manual
Original Instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Allen-Bradley 1606-XLE120F and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rockwell Automation Allen-Bradley 1606-XLE120F

  • Page 1 Power Supply - 48V, 2.5 A, 120 W, Single-phase Input Catalog Number 1606-XLE120F Reference Manual Original Instructions...
  • Page 2 If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
  • Page 3: Table Of Contents

    Additional Resources ..........29 Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 4 Notes: Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 5: Terminology And Abbreviations

    This power supply can be used in a wide variety of applications due to its high immunity to transients and power surges, low electromagnetic emission, DC OK signal contact for remote monitoring, and large international approval package. Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 6: Specifications

    Size (W x H x D) Without DIN rail (1.26 x 4.88 x 4.02 in.) Weight 440 g (0.97 lb) — Catalog Numbers Catalog Numbers Descriptions 1606-XLE120F Power supply 1606-XLA-XLE Wall/panel mount bracket Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 7: Ac Input

    Input Current, typ 1.5 A 1.25 0.95 a) 100V AC b) 120V AC c) 230V AC 0.75 0.85 (a) 100V AC (b) 120V AC 0.25 (c) 230V AC Output Current Output Current 0.75 0.25 0.5 Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 8: Dc Input

    25 °C (77 °F) Ambient and 25 °C (77 °F) Ambient 50 ms/DIV Input 50 ms/DIV Input current current 2 A/DIV 2 A/DIV Input Input voltage voltage 200V/DIV 200V/DIV Output voltage Output voltage Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 9: Output

    Figure 10 - Dynamic Output Current Capability, Typ Output Voltage Adjustment Output Voltage (dynamic behavior, < 12 ms) Range Adjustment Range A: continuous current B: intermittent current Output Current Output Current 0.5 1 3.5 4 10 A Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 10: Hold-Up Time

    Maximal 60V DC 0.3 A, 30V DC 1 A, 30V AC 0.5 A, resistive load Contact ratings < > Minimal permissible load: 1 mA at 5V DC 100 ms 1 ms 1...4 ms Isolation voltage Dielectric Strength on page open closed open closed Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 11: Efficiency And Power Losses

    Figure 17 - Efficiency Versus Input Voltage at 48V, 2.5 A, Typ Figure 18 - Losses Versus Input Voltage at 48V, 2.5 A, Typ Efficiency Power Losses 11 W Input Voltage Input Voltage 264V AC 264V AC Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 12: Functional Diagram

    The DC OK relay contact is synchronized with the DC OK Status Indicator. See DC OK Relay Contact on page 10 details. Input Terminals (screw terminals) N, L Line input PE (Protective Earth) input Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 13: Connection Terminals

    Figure 21 - Daisy Chaining of Outputs Figure 22 - Using Distribution Terminals Distribution Terminals Power Power Supply Supply Power Power Supply Supply Load Load Output Output Output Output max 25 A continuous Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 14: Lifetime Expectancy

    At 48V, 2.5 A and 40 °C (104 °F); 78,000 hr 80,000 hr 86,000 hr Ground Fixed GF40 At 48V, 2.5 A and 25 °C (77 °F); 105,000 hr 107,000 hr 115,000 hr Ground Fixed GF25 Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 15: Electromagnetic Compatibility

    PFC converter 30…140 kHz Input voltage and output load dependent Main converter 60…140 kHz Output load dependent Auxiliary converter 30…60 kHz Output load dependent DC OK relay converter 18…25 kHz Output voltage dependent Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 16: Environment

    Allowed Output Current at 48V 2.5 A 2.5 A 1.9 A A: 85...264V AC, continuous B: short term Altitude 2000 m 5000 m 70 °C 110 kPa 80 kPa 54 kPa Ambient Temperature (1) Atmospheric pressure Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 17: Safety And Protection Features

    (1) When testing input to DC OK, ensure that the max voltage between DC OK and the output is not exceeded (column D). We recommend connecting DC OK pins and the output pins together Output Earth, PE when performing the test. Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 18: Approvals And Fulfilled Standards

    Administrative Measures for the Restriction of the Use of Hazardous Substances in Electrical and RoHS (China RoHS 2) Electronic Products 25 years EAC Certificate EAC EurAsian Conformity - Registration Russia, Kazakhstan, and Belarus Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 19: Physical Dimensions And Weight

    Penetration protection Small parts like screws, or nuts with a diameter larger than 3.5 mm (0.138 in.) Figure 26 - Front View Figure 27 - Side View All dimensions in mm Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 20: Accessories

    Figure 29 - Left Front View Figure 30 - Right Back View Figure 31 - Wall/Panel Mounting, Front View Figure 32 - Hole Pattern for Wall Mounting Figure 33 - Wall/Panel Mounting, Side View Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 21: 1606-Xlsred Redundancy Module

    The buffer module can be added in parallel to the load circuit at any given point and does not require any control wiring. One buffer module can deliver 20 A additional current and can be added in parallel to increase the output ampacity or the hold-up time. Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 22: Peak Current Capability

    At 5 A for 50 ms and resistive load Peak current voltage dips Typically 48V dips to 41V At 12.5 A for 2 ms and resistive load Typically 48V dips to 34V At 12.5 A for 5 ms and resistive load Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 23: Charging Of Batteries

    Do not use power supplies in series in mounting orientations other than the standard mounting orientation. Leakage current, EMI, inrush current, and harmonics increase when using multiple devices. Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 24: Parallel Use To Increase Output Power

    • in mounting orientations other than the standard mounting orientation (terminals on bottom of the unit) • altitude Leakage current, EMI, and inrush current increase when using multiple devices. Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 25: Parallel Use For Redundancy

    Figure 39 - 1+1 Redundant Configuration for 2.5 A Load Current with a Dual Redundancy Module Failure Monitor Output Input Output Input 48V, 2.5 A 48V, 2.5 A Redundancy Module Power Power Supply Supply Output Input Input L N PE L N PE 2.5 A Load Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 26: N+1 Redundancy

    +10% 240V Ensure that the wire that is connected to the N-terminal, is appropriately fused. The maximum allowed voltage between a Phase and the PE must be below 300V AC. Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 27: Use In A Tightly Sealed Enclosure

    Temperature inside the box 39.1 °C (102.38 °F) 40.5 °C (104.9 °F) Temperature outside the box 25.8 °C (78.44 °F) 25.4 °C (77.72 °F) Temperature rise 13.3 K (23.94 °F) 15.1 K (27.18 °F) Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 28: Mounting Orientations

    Horizontal with Input on the Left +70 °C Ambient Temperature Allowed Output Current at 48V Figure 46 - Mounting Orientation E: 1.5 A Horizontal with Input on the Right +70 °C Ambient Temperature Rockwell Automation Publication 1606-RM116A-EN-P - September 2020...
  • Page 29: Additional Resources

    Power Supply - 48V, 2.5 A, 120 W, Single-phase Input Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Switched Mode Power Supply Specifications Technical Data, publication Provides specifications for Bulletin 1606 products and applications.
  • Page 30 At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.