TEST RUNNING
Cooling Unit
Model
For Evaporator Fan Motor
Overcurrent Relay
Condensing Unit
Models
For Compressor
High Pressure switch
Cut-Out
Cut-In
Low Pressure switch
Cut-Out
Cut-In
Overcurrent Transformer
Cut-Out
Internal Thermostat
Cut-Out
Cut-In
CCP Timer for Compressor
(built-in PCB)
No.1
No.2
For Evaporator Fan motor
Overcurrent Relay
For Condenser Fan motor
Internal Thermostat
Cut-Out
Cut-In
For Control Circuit Fuse
Capacity
29
Table 4. Safety and Control Device Setting
RAS-4U2S
RAS-5U2S
A
1.3
RAS-
RAS-
NP4CTS
NP5CTS
E406DH E506DH E626DH
MPa
4.15
4.15
2
kg/cm
G
42.3
42.3
MPa
3.2
3.2
2
kg/cm
G
32.6
32.6
MPa
0.4
0.4
2
kg/cm
G
4.1
4.1
MPa
0.7
0.7
2
kg/cm
G
7.1
7.1
A
8.3
10.6
° C
130
130
° C
108
108
min
3
3
min
A
° C
160
160
° C
130
130
A
2.5
2.5
RAS-6U2S
RAS-8U2S
Manual Reset, Adjustable
1.3
1.8
RAS-
RAS-
RAS-
NP6CTS
NP8CTS
NP9CTS
E506DH /
E856DH
E406DH
Automatic Reset, Non-Adjustable
4.15
4.15
42.3
42.3
3.2
3.2
32.6
32.6
Automatic Reset, Non-Adjustable
0.4
0.4
4.1
4.1
0.7
0.7
7.1
7.1
Automatic Reset, Non-Adjustable
13.0
18.0
8.3/10.6
Automatic Reset, Non-Adjustable
130
130
108
108
Non-Adjustable
3
3
Automatic Reset, Non-Adjustable
160
160
130
130
2.5
2.5
RAS-9U2S
1.8
3.6
RAS-
RAS-
NP10CTS
NP13CTS
E856DH /
E506DH
E506DH
4.15
4.15
4.15
42.3
42.3
42.3
3.2
3.2
3.2
32.6
32.6
32.6
0.4
0.4
0.4
4.1
4.1
4.1
0.7
0.7
0.7
7.1
7.1
7.1
10.6
18.0/10.6
130
130
130
108
108
108
3
3
3
3.5
3.5
3.5
6.0
160
160
160
130
130
130
2.5
2.5
2.5
RAS-10U2S
3.6
RAS-
NP15CTS
E856DH
4.15
42.3
3.2
32.6
0.4
4.1
0.7
7.1
18.0
130
108
3
3.5
6.0
160
130
2.5