Selected Pipes - Pipe sizes should be selected according to the "Refrigerant Piping Size and Charging
Data" in Technical CatalogⅠ and Ⅱ.
Piping Accessories - Confirm that the prepared piping accessories such as a filter-dryer, a sight glass,
a solenoid valve, insulation material and fittings have been correctly selected according to the conditions
specified in Table 1.
Model
RAS-NP4US+RAS-NP4CTS
RAS-NP5US+RAS-NP5CTS
RAS-NP6US+RAS-NP6CTS
RAS-NP8US+RAS-NP8CTS
RAS-NP9US + RAS-NP9CTS
RAS-NP10US + RAS-NP10CTS
RAS-NP13US + RAS-NP13CTS
RAS-NP15US + RAS-NP15CTS
A: The condensing unit is installed below the cooling unit.
B: The condensing unit is installed above the cooling unit.
* : Maximum Length without Solenoid Valve Control.
** : Maximum Length with Solenoid Valve Shut-Off Control.
Flare size - For piping and connection section, use R410A corresponding items. Sizes of flare nuts and
flares at the front end of the copper tubing also should change. Select according to the following
specifications.
Flare sizes
Tightening Flare Nut - When tightening the flare nut, utilize two spanners to require tightening torque as
shown below:
Tightening Work of Flare Nut
Refrigerant Piping
Table 1. Refrigerant Piping Limitation
Refrigerant Cycle
(Compressor Model)
E406DH
E506DH
E626DH
E856DH
No. 1: E506DH
No. 2: E406DH
No. 1: E506DH
No. 2: E506DH
No. 1: E856DH
No. 2: E506DH
No. 1: E856DH
No. 2: E856DH
Copper pipe
diameter dØ
9.53
12.7
15.88
19.05
Pipe Size
(mm)
9.53
12.7
15.88
19.05
REFRIGERANT PIPING
Maximum Lift (m)
A
B
15
25
15
25
15
25
15
25
15
25
15
25
15
25
15
25
15
25
15
25
15
25
15
25
Unit: mm
+0
A size
-0.4
R-22
R410A
13.0
13.5
16.2
16.5
19.4
19.5
23.3
24.0
Tightening Torque (kg-cm)
R-22
400
600
800
1,000
Maximum Equivalent
Piping Length
- One Way - (m)
*5/**30
*5/**30
*5/**30
*5/**30
*5/**30
*5/**30
*5/**30
*5/**30
*6/**30
*6/**30
*6/**30
*6/**30
R410A
400
600
800
1,000
20