Kaiterra Sensedge BACnet User Manual page 3

Smart air quality monitor

Advertisement

Kaiterra
www.kaiterra.com
2.
Setting up BACnet on the Sensedge
A. Turning on BACnet
By default, the BACnet feature on the Sensedge is not turned on.
Navigate to Settings –> Device Details –> Connectivity –> BACnet/IP to turn on the feature.
B. Setting the Device ID
On the Settings –> Device Details –> Connectivity –> BACnet/IP screen, the Device ID is customizable.
This Device ID is used to identify the device in the system, therefore, each Sensedge should have a unique
Device ID, and the Device ID should also be different from other devices in the same system.
A default Device ID is already provided in the Device ID field. This is a randomly generated number. It is
recommended to customize your own device ID when you have a huge system, so you can manage your
system in a more structured manner.
The range of allowed Device IDs is 0-4194302.
It is recommended to set the Device ID on site during or after installation, so it is easier to keep track of
the Device ID and installation locations.
C. Setting UDP port
On the Settings –> Device Details –> Connectivity –> BACnet/IP screen, the UDP port is customizable.
The default UDP port is filled in as 47808, which is a commonly used UDP port for BACnet/IP.