To reduce risk of injury, please use the proper recommended cable size as listed below
Table 6.0 –Wiring Sizing
6.2 – Connecting the Load Output Connection
Please follow below steps to implement AC load output connection:
•
Strip approximately ½" of the insulation on each of the conductors.
•
Insert AC output wires according to polarities indicated on terminal block and tighten the terminal
screws.
1. GND (Ground) Green
2. N (Neutral) White
3. L2 Red
4. L1 Black
4
3
2
1
7.0 – Battery Connection
The SimpliPHI Inverter is designed for integration with all SimpliPhi battery products, including PHI, AmpliPHI,
and SimpliPHI. Other batteries may be paired with the SimpliPHI Inverter. Make sure that you follow battery
manufacturers integration guides, settings and installation manuals for pairing with the SimpliPHI Inverter. If
using a smaller battery bank, adjustments to the charge/discharge settings will need to be made to avoid
damage to the batteries.
Before connecting to batteries install separately a 60 VDC/200 ADC circuit breaker between the inverter and
the batteries.
© SIMPLIPHI POWER
Suggested Cable Requirement for AC Wire
Nominal Grid Voltage
AWG
| 16 |
120/240 VAC
10 - 6
REV2022007071630