Power Supply Wiring; Connecting Remote Controller, Indoor And Outdoor Transmission Cables; Connecting Electrical Connections; Setting Addresses - Mitsubishi Electric CITY MULTI PDFY-P20VM-E Installation Manual

Air-conditioners for building application indoor unit
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
2. Remote controller cables
Types of cables
2-core cable (unshielded)
Cable diameter
0.3 to 1.25 mm
Length
Less than 200 m

8.1. Power supply wiring

Power supply cords of appliances shall not be lighter than design 245 IEC 57
or 227 IEC 57.
A switch with at least 3 mm contact separation in each pole shall be provided
by the Air conditioner installation.
Power cable size: more than 1.5 mm
[Fig. 8.1.1] (P.4)
A Switch 16 A
C Indoor unit
D Total operating current be less than 16 A
E Pull box
[Selecting non-fuse breaker (NF) or earth leakage breaker (NV)]
To select NF or NV instead of a combination of Class B fuse with switch, use the
following:
In the case of Class B fuse rated 15 A or 20 A,
NF model name (MITSUBISHI): NF30-CS (15 A) (20 A)
NV model name (MITSUBISHI): NV30-CA (15 A) (20 A)
Use an earth leakage breaker with a sensitivity of less than 30 mA 0.1 s.
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using
fuse, wire or copper wire with too large capacity may cause a risk of mal-
function or fire.
8.2. Connecting remote controller, indoor
and outdoor transmission cables
Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
Install a remote controller following the manual supplied with the remote con-
troller.
Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller.
(Non-polarized 2-wire)
Connect the remote controller's transmission cable within 10 m using a 0.75 mm
core cable. If the distance is more than 10 m, use a 1.25 mm
[Fig. 8.2.1] (P.4) MA Remote controller
[Fig. 8.2.2] (P.4) M-NET Remote controller
A Terminal block for indoor transmission cable
B Terminal block for outdoor transmission cable
C Remote controller
DC 9 to 13 V between 1 and 2 (MA remote controller)
DC 24 to 30 V between M1 and M2 (M-NET remote controller)
Notes:
*1 Put the transmission cable earth via the outdoor unit's earth terminal
to the ground.
*2 If the remote controller cable exceeds 10 m, use a 1.25 mm
cable over the exceeded portion, and add that exceeded portion to within
200 m.
*3 The BC controller is required only for simultaneous cooling and heating
series R2.
[Fig. 8.2.3] (P.4) MA Remote controller
[Fig. 8.2.4] (P.4) M-NET Remote controller
A Non-polarized
C Remote Controller
The MA remote controller and the M-NET remote controller cannot be used at
the same time or interchangeably.
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover.
Pinching the wiring may cut it.
MA remote controller
2
2
B Overcurrent protection 16 A
2
junction cable.
2
diameter
B Upper level (TB15)
D Lower level (TB5)
Non-shielding wire for up to 10 m; the same specifications as "1." Wiring
transmission cables for more than 10 m
2
0.3 to 1.25 mm
Add any portion in excess of 10 m to within the longest allowable trans-
mission cable length 200 m (Shielding portion is more than 1.25 mm
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension
may break, or overheat and burn.
Fix power source wiring to control box by using buffer bushing for tensile force.
(PG connection or the like.) Connect transmission wiring to transmission ter-
minal block through the knockout hole of control box using ordinary bushing.
After wiring is complete, make sure again that there is no slack on the connec-
tions, and attach the cover onto the control box in the reverse order removal.
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnec-
tion, heating or fire result.

8.3. Connecting electrical connections

(Be sure to prevent terminal screws from loosening.)
1. Remove 2 screws which secures the terminal bed box cover using a screw-
driver.
[Fig. 8.3.1] (P.4)
A Cover
2. As shown at 2, wire the power supply, transmission cable and remote control-
ler. There is no need to remove the terminal bed box.
[Fig. 8.3.2] (P.4)
C Terminal bed for transmission cable
D Transmission cable
(To terminal bed for remote controller, indoor unit and BC controller)
E To single-phase power supply
G To terminal bed for outdoor transmission cable
(Use shielding earth cable
H Non-polarity
J DC 24 to 30 V
Fix power source wiring to control box by using buffer bushing for tensile force.
(PG connection or the like.) Connect transmission wiring to transmission ter-
minal bed through the knockout hole of control box using ordinary bushing.
3. After wiring is complete, make sure again that there is no slack on the connec-
tions, and attach the cover onto the control box in the reverse order of removal.
Caution:
Wire the power supply so that no tension is imparted. Otherwise disconnec-
2
tion, heating or fire may result.

8.4. Setting addresses

(Be sure to operate with the main power turned OFF.)
[Fig. 8.4.1] (P.4)
<Address board>
There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is "3", remain SW12 (for over 10) at "0", and match
SW11(for 1 to 9) with "3".
2 How to set branch numbers SW14 (Series R2 only)
Match the indoor unit's refrigerant pipe with the BC controller's end con-
nection number. Remain other than R2 at "0".
The rotary switches are all set to "0" when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
The determination of indoor unit addresses varies with the system at site. Set
them referring to technical data.
Note:
Please set the switch SW5 according to the power supply voltage.
Set SW5 to 240 V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts, set SW5 to 220 V side.
8.5. Sensing room temperature with the
built-in sensor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the air flow at a time when the heating
thermometer is OFF.
M-NET remote controller
B Cover securing screw (2 places)
F Terminal bed for power supply
on outdoor unit side.)
I Network remote controller
2
)
11

Advertisement

Table of Contents
loading

Table of Contents