Delete user by input 10-digit format card number:
21, 10# (10-digit format number) #, 10# (10-digit format number) #, ...
Delete user by input ID number
22, (ID) #, (ID number) #, ...

4.1.10 Set open door methods

30, 0#, open door by card, you can open door by user card, but cannot open door by user PIN.
30, 1#, open door by card + PIN, read user card first, then input user PIN to open door.
30, 2#, default value, open door by cards or PIN, read user card or input user PIN to open door.
Note: Super-open-card or Super-open-password is not affected by any open door method; you can open door at any time.

4.1.11 Set Multi-card to open door

31, 1#, default value, read 1 card to open door.
31, (2-10)#, read 2~10 cards in turn to open door(The open door method must set to: open door by card).

4.1.12 Set lock working mode

32, 0#, default value, set lock to Delay mode. After an unlock operation, the lock is opened , then the lock will be closed
automatically after a few moment of delay. Apply to normal open.
32, 1#, set lock to Switch mode. After an unlock operation, the lock will latch open until another unlock operation again,
the lock will lock, and so on.
32, 2#, set lock to Normal-open mode. Under this mode, the lock will latch open, not controlled by other unlocking action.
If the user doesn't want to use the Normal-open mode, the administrator will need to change the mode to the other two modes.
Note: A better way to implement the Normal-open mode is using a Normal-open card in the first mode, it can switch to
Normal-open mode and normal status quickly. For the programming of Normal-open card, see the relevant chapter of
admin cards and their operation.

4.1.13 Set Limits User Mode

33, 0#, disable users to use.
33, 1#, default value, enable users to use.
Notes: A better way to implement the limits of user mode is operation by Authorization-card, it can switch to disable and en-
able users to operate quickly. The operation of Authorization-card, see relevant chapter of admin cards operation.

4.1.14 Set Open-time

34, 0#, set Open-time to 50mS, apply to electrically controlled lock for external instantaneous large current
34, (1-999) #, the default value is 2, set Open-time from 1 to 999S.

4.1.15 Door Ajar Alarm Period

35, (0-99) #, the default value is 10, set the time that notifies when the user has not closed the door after opening it.
When the door is left open more than (how many) seconds the buzzer will begin to beep for notification.
36, (0-99) #, the default value is 10, set the duration limit for beeping.
Note: If you don't need notification, can set the time for warning to 0.
CV-550 SPK V3 REFERENCE MANUAL
I NSTAL LATIO N INST RUCT IO NS