Eaton 9E10000i Manual page 15

Table of Contents

Advertisement

3.3.3 EBM W
C
IRING
ONNECTION
It is possible to connect more than one EBM in order to achieve any level of autonomy without mains power. Connect any Battery
Boxes in a cascade as shown in the figure below:
1. CONNECTION: Use 3 cables with 10 mm
2. Connect the wires to the relative terminals, following exactly the instructions given below:
For 9E6Ki, 9E10Ki, 9E10KiXL
a -
Make sure that the fuse holder of the external battery box is open.
b -
Connect the earth (PE) wire to EBM's earth (PE) screw
c -
Connect the positive (+) branch wire to EBM's positive (+)
d -
Connect the negative (-) branch wire to EBM's negative (-) terminal.
The suggested tighten force is 1.6Nm.
Versions 9E6Ki, 9E10Ki, 9E10KiXL
Fig.3-9 EBM terminal connection for 9E6Ki,
9E10Ki, 9E10KiXL With Single EBM
Note: For 9E15Ki, 9E20Ki, 9E20KiXL EBM wiring connection, you should check the 9EEBM manual in EBM
package.
2
section (Earth, +, N and -)
(Detailed wiring diagram see fig 3-9~10)
Fig.3-8 EBM terminal view (Fuse for 9E6Ki,
9E10Ki, 9E10KiXLwithout Neutral)
terminal.
Fig.3-10 EBM terminal connection for 9E6Ki,
9E10Ki, 9E10KiXL With Mutliple EBM
Page 15

Advertisement