PT100 Temperature Sensor Gateway SIG-5560 User Manual Version 1.0 Sollae Systems https://www.ezTCP.com...
Page 2
SIG-5560 User Manual Ver. 1.0 This symbol, found on your product or on its packaging, indicates that this product should not be treated as household waste when you wish to dispose of it. Instead, it should be handed over to an applicable collection point for the recycling of electrical and electronic equipment.
SIG-5560 User Manual Ver. 1.0 Overview 1.1 Introduction SIG-5560 industrial PT100 Temperature Sensor Gateway. This product consisting of a PT100 connection port and an FND(Flexible Numeric Display) for displaying a temperature. Users can remotely monitor the temperature measured by the sensor which is connected to this product by using Modbus/TCP.
SIG-5560 User Manual Ver. 1.0 1.3 Specification Analog Input Input Type 3-wire PT100 sensor (α=0.00385 Ω/(Ω·°C)) Resolution 16 bits Number of Ports 1 port Network Physical Interface Network Interface 10Base-T/100Base-TX Ethernet (RJ45) Ethernet Speed Auto Sense 1:1 or Cross-over Cable Auto Sense...
SIG-5560 User Manual Ver. 1.0 1.4 Interface Figure 1-2 Interface 1.4.1 Power SIG-5560 requires DC5V power supply whose specification is as follows: Figure 1-3 Power - 6 - https://www.ezTCP.com...
SIG-5560 User Manual Ver. 1.0 1.4.2 Ethernet SIG-5560 provides 10/100Mbps Ethernet. The pin assignment is as follows: Figure 1-4 Ethernet 1.4.3 PT100 Connection Port This port is interfaced with a 3.5mm pitch 3-pole terminal block. How to connect a PT100 sensor to this port is as follows: Figure 1-5 Connection with a PT100 sensor ⚫...
SIG-5560 User Manual Ver. 1.0 1.4.4 LED SIG-5560 provides 4 LEDs for indicating status. Figure 1-6 4 LEDs LED operations according to each state are as follows: When the supplied power is stable: PWR When the supplied power is NOT stable: PWR...
SIG-5560 User Manual Ver. 1.0 1.4.5 Function Button This button is used to implement a factory reset. 1.4.6 Setup Port This port is used for making a connection with a PC via USB cable. - 9 - https://www.ezTCP.com...
SIG-5560 User Manual Ver. 1.0 Preparation 2.1 Installing the Setting Tool You need a program which is called spFinder to use this product. Download the program on our web site and install it on your PC. Functions of the spFinder are as follows: ⚫...
SIG-5560 User Manual Ver. 1.0 Settings 3.1 Network 3.1.1 Obtain an IP address automatically This product can automatically obtain an IP address by DHCP. A DHCP server is required to use this. Figure 3-1 Obtain an IP address automatically ⚫ Select the [Obtain an IP address automatically].
SIG-5560 User Manual Ver. 1.0 3.1.2 Use a Static IP address You can set a static IP address to this product. Figure 3-2 Use a static IP address ⚫ Select the [Use static IP address]. ⚫ Set the [Local IP address], [Subnet mask], [Gateway IP address] and [DNS IP address].
SIG-5560 User Manual Ver. 1.0 3.2 General Figure 3-3 General 3.2.1 Comments This setting is for storing the product description. The maximum setting size of this item is 32 bytes. 3.2.2 TCP ⚫ Connection Mode This item selects the TCP connection method. You can choose between TCP Server and TCP Client.
SIG-5560 User Manual Ver. 1.0 ⚫ Connection Timeout (Unit: sec) This item is to set a timeout for terminating a TCP connection. If there is no valid Modbus/TCP data communication during the time set in this item, the TCP connection is terminated. The unit is seconds and can be set between 0 and 3600.
SIG-5560 User Manual Ver. 1.0 3.3 Security Figure 3-4 Security 3.3.1 Password Both ID and password are required to access this product. Note that changing the default password to another is highly recommended for security. The password should be longer than 8 characters.
SIG-5560 User Manual Ver. 1.0 ⚫ Remote access If this item is checked, the product can be connected from the remote network. For security, this item is unchecked by default. 3.3.4 Client ID This is NOT available for this product.
SIG-5560 User Manual Ver. 1.0 Management 4.1 Checking Status This is a function to view the current status of the product. Information in the [Status] window automatically updated every second. After searching connecting the product with spFinder, press the [Status] button to display this window.
SIG-5560 User Manual Ver. 1.0 4.1.2 Communication Status ⚫ Communication Status Window This area shows some communication status of your product. This area is refreshed every second. Figure 4-2 Communication Status Window ⚫ TCP STATE Status Description LISTEN Listen CLOSED...
SIG-5560 User Manual Ver. 1.0 ⚫ DEVICE STATISTICS Item Description TCP0~3 The byte count of TCP data: TX, RX The byte count of outgoing TCP data The byte count of incoming TCP data Current temperature (the lowest, the highest temperature)
SIG-5560 User Manual Ver. 1.0 4.2 Firmware Change New firmware can be released when adding functions or fixing bugs. If you are using old firmware, you can upgrade it to the latest version. Firmware can be upgraded online or manually via spFinder.
SIG-5560 User Manual Ver. 1.0 4.2.2 Manual Upgrade Figure 4-4 Manual Upgrade ⚫ Download a Firmware file to your PC. ⚫ Search and connect to your product by spFinder. ⚫ Click [Advanced] > [Firmware Change] menu. ⚫ Select to [Manual upgrade] on the [Firmware Upgrade] window.
SIG-5560 User Manual Ver. 1.0 4.3 Console The console function analyzes and displays the Modbus frames sent and received by the product. After searching and connecting the product with spFinder, click [Console] in the [Advanced] menu to display the console window. When you open this window, the spFinder connects to the product and keeps the connection until you close the window or time out.
SIG-5560 User Manual Ver. 1.0 the Output tab ⚫ dump off Pressing this button stops printing communication data out on the network to the Output tab ⚫ reset stat Press this button to reset all the communication status information statistics of the product.
SIG-5560 User Manual Ver. 1.0 4.5 Factory Reset Performing the Factory Reset, you can restore all the settings to the default including the password. Follow the procedure below by checking the status of RUN LED. 1. Press and immediately release the function button.
SIG-5560 User Manual Ver. 1.0 Register Map 5.1 Read Only 5.1.1 Temperature Value Register This register is for storing the most recently measured temperature value. HMI Addressing Division Address Word Count Type Function Code Example Port 0 Integer 30001 Table 5-1 Temperature Value Register The temperature value is rounded to one decimal place and stored in multiples of 10.
SIG-5560 User Manual Ver. 1.0 5.1.4 The Highest Temperature Value Register This register is for storing the highest value among measured temperatures. HMI Addressing Division Address Word Count Type Function Code Example Port 0 Integer 30033 Table 5-5 5.1.4 The Highest Temperature Value Register The highest temperature value is rounded to one decimal place and stored in multiples of 10.
SIG-5560 User Manual Ver. 1.0 5.1.8 Device Information Register HMI Addressing Division Address Word Count Type Function Code Example Vendor Name ASCII 40401 Product Code ASCII 40408 Version ASCII 40412 Comment ASCII 40417 Uptime ASCII 40433 MAC Address ASCII 40443...
SIG-5560 User Manual Ver. 1.0 5.2 Read / Write 5.2.1 Reset The Lowest / The Highest Temperature Value Register This register is for initializing 4 register values: the lowest temperature value register, the lowest temperature value register (FP32), the highest temperature value register and the highest temperature value register (FP32).
Technical Support and Warranty 6.1 Technical Support If you have any question regarding operation of the product, visit Customer Support FAQ corner and the message board on Sollae Systems’ web site or send us an email at the following address: ⚫ E-mail: support@eztcp.com...
⚫ Specifications of the product are subject to change without prior notice for performance improvement. ⚫ Sollae Systems does not guarantee successful operation of the product if the product was used under conditions deviating from the product specifications. ⚫ Reverse engineering of firmware and applications provided by Sollae Systems is prohibited.
(including, without limitation, damages for loss of profit, operating cost for commercial interruption, loss of information, or any other financial loss) from the use or inability to use the SIG-5560 even if Sollae Systems Co., Ltd. or its distributors have been informed of such damages.
à leur propriétaire et Fabricant respectif. ⚫ Conditions d’utilisations et limite de responsabilité En aucun cas Sollae Systems Co., Ltd. ou un de ses distributeurs ne pourra être tenu responsable de dommages quels qu'ils soient (intégrant, mais sans limitation, dommages...
Page 34
SIG-5560 sans que la responsabilité de Sollae Systems Co., Ltd. et de ses distributeurs ne puissent être mise en cause, ni que le boîtier SIG-5560 puisse être échangé au titre de la garantie.