10. TROUBLESHOOTING

Cause of fault message
Display symbol
Discharge LED
No display
extinguished
Power device failure
PF01
during acceleration
Power device failure
PF02
during constant
frequency operation
Power device failure
PF03
during deceleration
Power device failure
PF04
during stand-by
EEP1
EEPROM access error
EEPROM check-sum
EEP2
error
contents
Review the power system.
Check that MCCB has been
turned on or no poor contact.
The acceleration time is too short.
Boost voltage too high
Check the motor is locked or the
load is too heavy
Disconnecting the output wiring
W.V.U.
Restart (Run) the inverter check for
the same message
Check for sudden change in load
Check that the ambient
temperature is too high
The load inertia is excessive
Over voltage
Check around the noise source
Power supply voltage is too high
Communication reset error
Rework with previous process, if
same message happen again.
Rework with previous process, if
same message happen again.
Check point
86
Suggested remedy
Turned on or Replace
MCCB
Increase the acceleration
time
Reduce CD21 contents
Reduce the load factor
Repair
Eliminate sudden change
in load
Reduce the ambient
temperature
Increase the deceleration
time
Connect braking resistor
Remove the cause
Reduce the voltage
Refer to address 100
description
Repair
Repair