Gas Inlet Connection; Electrical Power Supply; Installation Of Duct Connection Pops - Kaden KEX Series Installer Manual

Ducted gas heaters
Table of Contents

Advertisement

Kaden Installer's Manual
Ducted Gas Heaters
If fitting the heater to elevated heights such as a roof, use suitable lifting equipment.
NOTE
1.4

GAS INLET CONNECTION

All piping must be in accordance with AS/NZS 5601 and any local gas regulations.
The connection point for all Kaden model heaters is a female G3/4 compression fitting to AS 3688. For KEX
models this is located at the base of the heaters outer cabinet, and for KUN models the gas feed tube is supplied
loose in the control compartment and MUST BE fitted to suit the installation.
A gas cock shall be fitted in the gas line adjacent to the heater and in a convenient location so it can be turned
OFF quickly and easily.
The gas supply shall in no way interfere with any servicing of the heater.
The gas supply must be installed by a licensed gas fitter. The gas pipe and gas meter should be
sized so the heater can maintain its required incoming gas pressure at maximum consumption
with all other gas appliances operating at their maximum capacity at the same time as the heater.
NOTE
1.5

ELECTRICAL POWER SUPPLY

The heater is pre-wired with a 3-pin plug and lead, and shall be plugged into a standard 10 Amp 220 to 240 volt
fixed switched socket outlet adjacent to the heater, in a convenient location so it can be turned OFF quickly and
easily.
A qualified electrician must install the 220 to 240 volt wiring according to local regulations.
NOTE
Switch OFF the power and unplug the heater before touching any wiring. If any electrical wiring is
damaged, it must be replaced by the manufacturer, its service agents or an electrically qualified
IMPORTANT
technician, in order to avoid a hazard.
The electricity supply must be 220 to 240 V at 50 Hz, and from an authorised power supplier. Generators should
never be used, as their output may be incompatible with, or prone to damage the heater's electronic components.
1.6

INSTALLATION OF DUCT CONNECTION POPS

On Kaden KUN Series heaters, the pops need to be fastened to the heater cabinet as follows:
Insert pops into the hole in the POP plate, ensuring the POP flange is placed over the prescribed wall of the
cabinet, refer to the "POP Installation Matrix" below.
Spread POP flange to fit tightly into the hole in the cabinet (the notch side overlapping the other).
Secure pops with the rivets supplied.
Series
KUN3
KUN4
KUN5
The POP is fitted to a POP plate for some models and a panel for others.
NOTE
8
POP Installation Matrix
Return Air
Number of walls
Installation POP
1
2
2
Number of walls
No Option
Inner Wall
Inner Wall
Table 1
Supply Air
Installation POP
2
Inner Wall
2
Inner Wall
2
Inner Wall