Networker Installation Kun4 & Kun5; Wiring The Networker To A Kun4 & Kun5 Heater - Kaden KEX Series Installer Manual

Ducted gas heaters
Table of Contents

Advertisement

8.1
NETWORKER INSTALLATION KUN4 & KUN5
8.1.1 Wiring the Networker to a KUN4 & KUN5 Heater
The Kaden Networker backing plate has 4 terminal points for the connection of control wires.
When connecting, use ONLY the two top terminals marked TW1 and TW2 or ONLY the two
IMPORTANT
bottom terminals also marked TW1 and TW2. NEVER use a combination of top and bottom
terminals when connecting to a single appliance.
For example, a Kaden Networker operating a Kaden cooler and a Kaden heater would have the
two bottom terminals connected to the heater and the two top terminals connected to the cooler.
When there is more than one Kaden appliance connected to a Kaden Networker, always ensure
that the TW1 and TW2 polarity is correct at both ends of the wire cable.
Networkers can be wired directly to KUN4 and KUN5 heaters as follows:
Run a twin wire cable (i.e. figure 8 cable - 0.75mm
Remove the backing plate from the Kaden Networker by unclipping it at the sides.
Draw the wires from the wall cavity and feed them through the opening in the backing plate.
Connect the cable to the terminal connections on the backing plate before mounting it to the wall Diagram 18.
Mount the backing plate onto the wall and then reassemble the controller.
Feed the cable through the grommet, located at a cabinet end.
Connect the other end of the cable to the terminals marked TW1 and TW2 on the heater's electronic control
module, refer to Diagram 18.
KUN5
For Networker connection to KUN3, KEX3 and KEX4 models a Kaden 539 interface is required,
Kaden Part No. 1621292
NOTE
Grommet for
control cable
access
Control Board
Diagram 18
) from the heater to the Networker.
2
TW1
TW1
TW2
TW1
TW2
TW1
TW2
TW2
Networker Back Plate